1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: MEMORANDUM TO: FROM: Technical Committee on Liquefied Petroleum Gases Kimberly Shea DATE: June 30, 2014 SUBJ: NFPA 58 Proposed TIA No Ballot Results According to 5.4 in the NFPA Regs, the final results show this TIA HAS NOT achieved the ¾ majority vote needed on both Question 1 (Technical Merit) and Question 2 (Emergency Nature). 30 Eligible to Vote 6 Not Returned (Belke, Bogan, Garza-Obregon, Hinske, Kastanas, Meyer) Technical Merit Emergency Nature: 13 Agree 12 Agree 10 Disagree (Fredenburg, Hoffmann, King, Mahnken, Mortimer, Osterhaus, Ribbs, Stainbrook, Wilson, Wolff-Klammer) 10 Disagree (Fredenburg, King, Mahnken, Mortimer, Osterhaus, Ribbs, Stainbrook, Wilson, Wolff-Klammer, Young) 1 Abstain (Barber) 2 Abstain (Barber, Hoffman) There are two criteria necessary to pass ballot [(1) affirmative ¾ vote and (2) simple majority] with both questions needing to pass ballot in order to recommend that the Standards Council issues this TIA. (1) In all cases, an affirmative vote of at least a simple majority of the total membership eligible to vote is required. This is the calculation for simple majority: 30 eligible 2 = = 16 (2) The number of affirmative votes needed to satisfy the ¾ requirement is: Question 1: 30 eligible - 6 not returned - 1 abstentions = = = 18 Question 2: 30 eligible 6 not returned - 2 abstentions = = 16.5 = 17 An appeal relating to a proposed Tentative Interim Amendment shall be filed 5 days after the notice of the Correlating Committee TIA ballot results are published in accordance with (c) and

2 TECHNICAL COMMITTEE LETTER BALLOT Question 1: I agree with the TECHNICAL MERITS of the Proposed TIA to revise and Table AGREE X DISAGREE* ABSTAIN* The arguments presented in the substantiation are more complex than should be allowed in the hurried consideration of a TIA. Much technical information cannot be verified in this brief review. It needs to be researched and discussed. AGREE X DISAGREE* ABSTAIN* The emergency nature cited (5.4 (e)) is not appropriate for this topic. Yes, it is an advance, but not in safeguarding property or life. _Richard Fredenburg June 20, 2014 Please return the ballot to kshea@nfpa.org no later than Thursday, June 19, 2014.

3 Shea, Kimberly From: Richard Hoffmann Sent: Tuesday, June 17, :52 PM To: Shea, Kimberly Cc: Tina Pellegrini Subject: NFPA 58 Comments - Proposed TIA Dear Kimberly Shea I have reviewed the proposed TIA and have several issues with it. 1. the alloy of choice is AA 6061, which is a good alloy. 2. the reported melting point is +1280F. This number represents the end of the melting range, where you have a puddle of aluminum on the bottom where it collected. The melting starts, for this alloy, at about 1080F. the melting would start throughout the alloy, at all low melting point constituents. 3. The use of threaded surfaces as shown in the attached photographs is not good, since aluminum is a poor "threading" alloy and galling / surface corrosion can occur, causing sealing issues on the threads. The counter to this is the mag lite flashlights, which have a good life, but the threading can be difficult. 4. The filter canister is identified as steel there will be a galvanic corrosion issue here with the aluminum being the anode, and corrosion could take place, depending on the environment the component is placed in. The question that I must ask is how long will the canister / filter housing always be steel? or will that someday switch to aluminum. Based on these comments, I cannot accept the technical merits of this proposed TIA. I have no comment on the "emergency" nature of this issue, however, I think it needs more discussion time. Richard Hoffmann Technical Chairman NFPA 58 1

4

5 TECHNICAL COMMITTEE LETTER BALLOT Question 1: I agree with the TECHNICAL MERITS of the Proposed TIA to revise and Table AGREE X DISAGREE* ABSTAIN* No explanation was given why higher melting point materials cannot be used for the filter heads. AGREE X DISAGREE* ABSTAIN* Why should the standard be lowered to allow use of aluminum filter heads? Glenn Mahnken June 17, 2014 Please return the ballot to kshea@nfpa.org no later than Thursday, June 19, 2014.

6 TECHNICAL COMMITTEE LETTER BALLOT Question 1: I agree with the TECHNICAL MERITS of the Proposed TIA to revise and Table AGREE XX DISAGREE* ABSTAIN* _There are current means available to filter LP fuel. This can and should be addressed during a normal cycle. AGREE XX DISAGREE* ABSTAIN* No emergency here. Frank J. Mortimer June 6, 2014 Please return the ballot to kshea@nfpa.org no later than Thursday, June 19, 2014.

7

8 Shea, Kimberly From: Sent: To: Subject: Phillip Ribbs Wednesday, June 11, :59 AM Shea, Kimberly Re: NFPA 58 Proposed TIA TECHNICAL COMMITTEE LETTER BALLOT Question 1: I agree with the TECHNICAL MERITS of the Proposed TIA to revise and Table AGREE x DISAGREE* ABSTAIN* Nothing was submitted to justify that all devices will be manufactured to this quality. Why not forged, cast, spun aluminum. This appears to be a proprietary submittal. AGREE x DISAGREE* ABSTAIN* This issue does not meet the level emergency. The subject should be vetted at an open TC meeting. Phillip H Ribbs Phillip H Ribbs 6/11/14 1

9 TECHNICAL COMMITTEE LETTER BALLOT Question 1: I agree with the TECHNICAL MERITS of the Proposed TIA to revise and Table AGREE X DISAGREE* ABSTAIN* _The use of aluminum bodies in liquid applications especially in pipelines at bulk plants have always been restricted due to the concerns about heat from fire exposure resulting in the failure of the body and the discharge of product from the failed body making a bad situation worse. There are other materials that are currently approved for liquid applications called out in table that more than likely could be used as a body for this product such as ductile iron, steel, malleable iron and brass to name a few. AGREE X DISAGREE* ABSTAIN* _There is no potential for loss of life, exposure of the public to a hazard or negative effect on over-all industry safety if this is not acted on immediately; this is not an emergency. David Stainbrook 5/5/14 Please return the ballot to kshea@nfpa.org no later than Thursday, June 19, 2014.

10

11 TECHNICAL COMMITTEE LETTER BALLOT Question 1: I agree with the TECHNICAL MERITS of the Proposed TIA to revise and Table AGREE X DISAGREE* ABSTAIN* If the section is revised to include the entire LP-Gas filtration system, it would also include the housing. This proposal should be for filter heads only. Also in section the minimum melting point of 1500 degrees F would still apply to the filter heads. Section would need to be revised and balloted to add filter heads as an exception. AGREE X DISAGREE* ABSTAIN* A new proposal need to be submitted based on my comments above. Edgar Wolff-Flammer 6/17/2014 Please return the ballot to kshea@nfpa.org no later than Thursday, June 19, 2014.

12 TECHNICAL COMMITTEE LETTER BALLOT Question 1: I agree with the TECHNICAL MERITS of the Proposed TIA to revise and Table XX AGREE DISAGREE* ABSTAIN* AGREE XX DISAGREE* ABSTAIN* _Finding a new product which is may be desirable does not constitute an emergency. William J. Young William J. Young Please return the ballot to kshea@nfpa.org no later than Thursday, June 19, 2014.

13 Shea, Kimberly From: Sent: Wednesday, June 18, :03 AM To: Shea, Kimberly Subject: Re: NFPA 58 Proposed TIA Ballot Reminder - Due June 19, 2014 Dear Kimberly, I have carefully considered the proposed TIA, which I fully understand. However as an overseas member of the committee on this occasion I consider it inappropriate to vote, and therefore abstain. For the benefit of the committee members I would like to bring to their attention the following situation relating to the use of aluminium components in LPG systems. I have personal experience of problems which can occur if the LPG is from a refinery which uses caustic soda for the removal of hydrogen sulphide. Any carry over of the caustic soda, if associated with water, causes an aggressive chemical reaction leading to the early failure of any aluminium components in the system. We addressed this problem in the UK by replacing the aluminium components with matching items machined from stainless steel. We worked closely with the UK licensee for Rego on many occasions. Best regards, Don Barber Principal & Senior Partner, Enmat International. On 17 June 2014 at 17:00 "Shea, Kimberly" <kshea@nfpa.org> wrote: Technical Committee on Liquefied Petroleum Gases: Please note that ballots on proposed TIA 1153 on the 2014 edition of NFPA 58 are due no later than Thursday, June 19, Kimberly Shea Administrator, Technical Projects NFPA 1 Batterymarch Park Quincy, MA

MEMORANDUM. Technical Committee on Liquefied Petroleum Gases. Subject: NFPA 58 Proposed Tentative Interim Amendment (TIA) No. 1153

MEMORANDUM. Technical Committee on Liquefied Petroleum Gases. Subject: NFPA 58 Proposed Tentative Interim Amendment (TIA) No. 1153 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: Technical Committee on Liquefied Petroleum Gases

More information

MEMORANDUM. NFPA Technical Committee on Liquefied Petroleum Gases. Subject: NFPA 58 Proposed Tentative Interim Amendment (TIA) No.

MEMORANDUM. NFPA Technical Committee on Liquefied Petroleum Gases. Subject: NFPA 58 Proposed Tentative Interim Amendment (TIA) No. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Liquefied Petroleum Gases

More information

6 Disagree (Drobnick, Dyson, Eblen, Gray, Mohla)

6 Disagree (Drobnick, Dyson, Eblen, Gray, Mohla) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Electrical Safety in the Workplace

More information

MEMORANDUM. Subject: NFPA 101 Proposed Tentative Interim Amendment (TIA) No.1114

MEMORANDUM. Subject: NFPA 101 Proposed Tentative Interim Amendment (TIA) No.1114 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Correlating Committee on Safety to Life (SAF-AAC)

More information

MEMORANDUM. Subject: NEC Proposed Tentative Interim Amendment (TIA) No. 1117

MEMORANDUM. Subject: NEC Proposed Tentative Interim Amendment (TIA) No. 1117 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NEC Correlating Committee Kimberly Shea Date: August

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 16 FROM: Kimberly Shea,

More information

MEMORANDUM. SUBJECT: NFPA 70E Proposed Tentative Interim Amendment (TIA) No. 1253R

MEMORANDUM. SUBJECT: NFPA 70E Proposed Tentative Interim Amendment (TIA) No. 1253R National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: National Electrical Code Correlating Committee Sarah

More information

MEMORANDUM. NFPA Correlating Committee on Professional Qualifications. Subject: NFPA 1006 Proposed Tentative Interim Amendment (TIA) No.

MEMORANDUM. NFPA Correlating Committee on Professional Qualifications. Subject: NFPA 1006 Proposed Tentative Interim Amendment (TIA) No. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Correlating Committee on Professional Qualifications

More information

MEMORANDUM. Subject: NFPA 1971 Proposed Tentative Interim Amendment (TIA) No.1159

MEMORANDUM. Subject: NFPA 1971 Proposed Tentative Interim Amendment (TIA) No.1159 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Correlating Committee on Fire and Emergency

More information

2015 Annual Revision Cycle Notice of a Consent Standard NFPA 1071

2015 Annual Revision Cycle Notice of a Consent Standard NFPA 1071 2015 Annual Revision Cycle Notice of a Consent Standard NFPA 1071 The Committee on Emergency Vehicle Technicians Professional Qualifications produced a First Revision Report for NFPA 1071, Standard for

More information

MEMORANDUM. Subject: NFPA 1917 Proposed Tentative Interim Amendment (TIA) No.1170

MEMORANDUM. Subject: NFPA 1917 Proposed Tentative Interim Amendment (TIA) No.1170 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Ambulances Yvonne Smith,

More information

MEMORANDUM. Subject: NFPA 259 Proposed Tentative Interim Amendment (TIA) No. 957

MEMORANDUM. Subject: NFPA 259 Proposed Tentative Interim Amendment (TIA) No. 957 MEMORANDUM To: From: Technical Committee on Fire Tests Gregory Harrington, Acting Staff Liaison Date: May 12, 2009 Subject: NFPA 259 Proposed Tentative Interim Amendment (TIA) No. 957 The attached proposed

More information

MEMORANDUM. NFPA Correlating Committee on Health Care Facilities. Subject: NFPA 99 Proposed Tentative Interim Amendment (TIA) No.

MEMORANDUM. NFPA Correlating Committee on Health Care Facilities. Subject: NFPA 99 Proposed Tentative Interim Amendment (TIA) No. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Correlating Committee on Health Care Facilities

More information

MEMORANDUM. NFPA Technical Committee on Electronic Safety Equipment. Subject: NFPA 1982 Proposed Tentative Interim Amendment (TIA) No.

MEMORANDUM. NFPA Technical Committee on Electronic Safety Equipment. Subject: NFPA 1982 Proposed Tentative Interim Amendment (TIA) No. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Electronic Safety Equipment

More information

National Fire Protection Association MEMORANDUM. Subject: NFPA 20 Proposed Tentative Interim Amendment (TIA) No. 1199

National Fire Protection Association MEMORANDUM. Subject: NFPA 20 Proposed Tentative Interim Amendment (TIA) No. 1199 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Pumps Elena Carroll,

More information

MEMORANDUM. NFPA Technical Committee on Wastewater Treatment Plants. Subject: NFPA 820 Proposed Tentative Interim Amendment (TIA) No.

MEMORANDUM. NFPA Technical Committee on Wastewater Treatment Plants. Subject: NFPA 820 Proposed Tentative Interim Amendment (TIA) No. MEMORANDUM To: From: NFPA Technical Committee on Wastewater Treatment Plants Joanne Goyette Date: March 25, 2011 Subject: NFPA 820 Proposed Tentative Interim Amendment (TIA) No. 1025 The attached proposed

More information

Supplemental Operating Procedures for the National Electrical Code Project

Supplemental Operating Procedures for the National Electrical Code Project Adopted by the NEC Correlating Committee on April 27, 2012. Approved by the Standards Council on August 9, 2012. Introduction (a) Preamble. The Operations of the (i.e., the NEC Correlating Committee (CC)

More information

Technical Committee on Tank Leakage and Repair Safeguards. SUBJECT: NFPA 329 Second Draft TC Final Ballot Results (F2014)

Technical Committee on Tank Leakage and Repair Safeguards. SUBJECT: NFPA 329 Second Draft TC Final Ballot Results (F2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Tank Leakage and Repair Safeguards Lawrence

More information

Technical Committee on Animal Housing Facilities. SUBJECT: NFPA 150 Second Draft TC Final Ballot Results (A2015)

Technical Committee on Animal Housing Facilities. SUBJECT: NFPA 150 Second Draft TC Final Ballot Results (A2015) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Animal Housing Facilities Tracy Vecchiarelli,

More information

M E M O R A N D U M. NFPA Technical Committee on Explosion Protection Systems

M E M O R A N D U M. NFPA Technical Committee on Explosion Protection Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Explosion Protection

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 1 FROM: Kimberly Shea, Administrator,

More information

Technical Committee on Electrical Equipment of Industrial Machinery (EEI-AAA)

Technical Committee on Electrical Equipment of Industrial Machinery (EEI-AAA) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Electrical Equipment of Industrial Machinery

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Project

More information

Table 6-4 Materials for Building Supply and Water Distribution Piping and Fittings Building Supply Water. Pipe and Distribution Referenced Standard(s)

Table 6-4 Materials for Building Supply and Water Distribution Piping and Fittings Building Supply Water. Pipe and Distribution Referenced Standard(s) July 9, 2009 Steve Nastruz Plumbing Inspector Seattle/King County Health Dept. 19600 20 th Avenue NW Shoreline, WA 98177 Re: IAPMO Standards Council Decision TIA UPC-005-09 Decision Date: July 9, 2009**

More information

M E M O R A N D U M. NFPA Technical Committee on Fire Service Occupational Safety and Health

M E M O R A N D U M. NFPA Technical Committee on Fire Service Occupational Safety and Health National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Fire Service

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 9 From: Kimberly Shea, Project Administrator

More information

According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Air Conditioning (AIC-AAA) Allan Fraser,

More information

SUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016)

SUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: NEC Code-Making Panel 17 FROM: Kimberly Shea, Administrator, Technical

More information

Report on Comments F2005 Copyright, NFPA NFPA 211 Report of the Committee on

Report on Comments F2005 Copyright, NFPA NFPA 211 Report of the Committee on Report on Comments F2005 Copyright, NFPA NFPA 211 Report of the Committee on Chimneys, Fireplaces, and Venting Systems for Heat-Producing Appliances Robert V. LeClair, Chair State of Maine, ME [E] Robert

More information

Technical Committee on Liquefied Natural Gas

Technical Committee on Liquefied Natural Gas Technical Committee on Liquefied Natural Gas AGENDA American Gas Association 400 North Capitol Street Washington, DC 20001 October 2, 2013 1. Chair s welcome, call to order, and opening remarks at 8:00

More information

ASC Z223 NFPA 54. DRAFT COMMITTEE MINUTES October 13-15, 2015 APPROVAL PENDING COMMITTEE ON NATIONAL FUEL GAS CODE

ASC Z223 NFPA 54. DRAFT COMMITTEE MINUTES October 13-15, 2015 APPROVAL PENDING COMMITTEE ON NATIONAL FUEL GAS CODE ASC Z223 NFPA 54 COMMITTEE ON NATIONAL FUEL GAS CODE DRAFT COMMITTEE MINUTES October 13-15, 2015. APPROVAL PENDING ASC Z223 NFPA 54 COMMITTEE ON NATIONAL FUEL GAS CODE Minutes ASC Z223 / NFPA 54 National

More information

Office of State Fire Marshal

Office of State Fire Marshal South Carolina Department of Labor, Licensing and Regulation Office of State Fire Marshal 141 Monticello Trail Columbia, SC 29203 Phone: 803-896-9800 Fax: 803-896-9806 www.llronline.com Licensing and Permitting

More information

Formal Interpretations/ Interprétation formelle

Formal Interpretations/ Interprétation formelle Formal Interpretations/ Interprétation formelle This section lists questions that individuals have submitted about a particular standard. Each question has been reviewed and answered by the appropriate

More information

Technical Committee on Tank Leakage and Repair Safeguards

Technical Committee on Tank Leakage and Repair Safeguards Technical Committee on Tank Leakage and Repair Safeguards NFPA 326 and NFPA 329 Second Draft Web/Teleconference Agenda April 9, 2014, 1:00 PM (EDT) to 2:00 PM (EDT) CALL IN INFORMATION and ONLINE LINK:

More information

MINUTES OF ROC MEETING Technical Committee on Multiple Burner Boilers Fall 2010 cycle SRP PERA Club 1 E. Continental Drive Tempe, AZ 85281

MINUTES OF ROC MEETING Technical Committee on Multiple Burner Boilers Fall 2010 cycle SRP PERA Club 1 E. Continental Drive Tempe, AZ 85281 MINUTES OF ROC MEETING Technical Committee on Multiple Burner Boilers Fall 2010 cycle SRP PERA Club 1 E. Continental Drive Tempe, AZ 85281 March 30, 2010 Attendance: Principal Members/Staff: Harold Skip

More information

Technical Committee on Liquefied Natural Gas

Technical Committee on Liquefied Natural Gas Technical Committee on Liquefied Natural Gas Minutes Bechtel Oil, Gas, & Chemicals Inc. 3000 Post Oak Blvd. Houston, TX 77056 March 11-12, 2014 Part I, Attendance: Principal Members and Staff: Jay Jablonski,

More information

COMMITTEE ON AGRICULTURAL DUSTS

COMMITTEE ON AGRICULTURAL DUSTS COMMITTEE ON AGRICULTURAL DUSTS TO: FROM: COMMITTEE ON AGRICULTURAL DUSTS G. R. Colonna, Staff Liaison DATE: February 12, 2014 SUBJ: Minutes of NFPA 61 Pre-First Draft Meeting (Conference Call), February

More information

City of Commerce City 2012 International Fire Code. Code Amendments

City of Commerce City 2012 International Fire Code. Code Amendments COMMUNITY DEVELOPMENT City of Commerce City 2012 International Fire Code Code Amendments The City of Commerce City adopted the 2012 Edition of the International Fire Code, including Appendix Chapters B,

More information

City of Tacoma Planning and Development Services

City of Tacoma Planning and Development Services City of Tacoma Planning and Development Services ORDINANCE NO. 28155 Adopt and Amend the City s Building Code; amending Title 2 of the Tacoma Municipal Code, implement the 2012 International Building,

More information

Supplemental Operating Procedures for the NFPA Committees on Safety to Life

Supplemental Operating Procedures for the NFPA Committees on Safety to Life Supplemental Operating Procedures for the NFPA Committees on Safety to Life Adopted by the Technical Correlating Committee on Safety to Life: January 2002 (letter ballot). Approved by the Standards Council:

More information

8, DAYS PRIOR TO THE ANNUAL SCHOOL ELECTION

8, DAYS PRIOR TO THE ANNUAL SCHOOL ELECTION 2014 Annual School Election and Annual School Election Runoff SEPTEMBER 16, 2014 Annual School Board Election A.C.A. 6-14-102(a)(1) Deadline to apply to register to vote Sunday, August 17, 2014* oactual

More information

Technical Committee on Electrical Equipment of Industrial Machinery (EEI-AAA)

Technical Committee on Electrical Equipment of Industrial Machinery (EEI-AAA) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Electrical Equipment of Industrial Machinery

More information

M E M O R A N D U M. NFPA 99 Second Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

M E M O R A N D U M. NFPA 99 Second Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Electrical Systems

More information

Any person who is disorderly or who, in the judgment of the Board, unreasonably disrupts the 5% test may be removed.

Any person who is disorderly or who, in the judgment of the Board, unreasonably disrupts the 5% test may be removed. Commissioners Doc_24 Attendance at the Board s 5% test shall be limited to the following: Board employees and agents Representatives of the State Board of Elections, the U.S. Attorney, the Illinois Attorney

More information

ALUMINIUM ROLLERS MADE IN ITALY

ALUMINIUM ROLLERS MADE IN ITALY ALUMINIUM ROLLERS MADE IN ITALY Alveolar aluminium rollers, diameter 60mm to 250mm (natural or anodized). Roller manufacturing will be completely based on customer's drawings. The rollers can be supplied

More information

TITLE 12 BUILDING, UTILITY, ETC. CODES CHAPTER 1 BUILDING CODE 1

TITLE 12 BUILDING, UTILITY, ETC. CODES CHAPTER 1 BUILDING CODE 1 12-1 TITLE 12 BUILDING, UTILITY, ETC. CODES CHAPTER 1. BUILDING CODE. 2. PLUMBING CODE. 3. ELECTRICAL CODE. 4. GAS CODE. 5. HOUSING CODE. 6. MODEL ENERGY CODE. 7. UNSAFE BUILDING ABATEMENT CODE. 8. MECHANICAL

More information

Enforcement and Compliance, International Trade Administration, Department of Commerce.

Enforcement and Compliance, International Trade Administration, Department of Commerce. This document is scheduled to be published in the Federal Register on 06/29/2018 and available online at https://federalregister.gov/d/2018-13565, and on FDsys.gov DEPARTMENT OF COMMERCE International

More information

JANUARY 28 & 29, 2015

JANUARY 28 & 29, 2015 2015 Annual Meeting JANUARY 28 & 29, 2015 The Roosevelt Hotel New Orleans Join us for this important industry event. Register online at www.lmoga.com. Meeting Information Whether onshore or offshore operations,

More information

The Therma Gauge Type H - FDEP EQ 730

The Therma Gauge Type H - FDEP EQ 730 The Therma Gauge Type H - FDEP EQ 730 Calibration: Consists of 3 pieces. Outer plastic piece, inner plastic piece, and a piece of paper in between. Optional glass inner piece is available. Red Lock Nut:

More information

Ph: Fax: East Philadelphia Street Ontario, California USA To:

Ph: Fax: East Philadelphia Street Ontario, California USA To: To: IAPMO Members and Other Interested Parties Date: August 2010 Enclosed is your 2010 Report on Proposals (ROP). These proposals were presented to the Plumbing Technical Committee who met in Milwaukee,

More information

NATIONAL ELECTRICAL CODE CORRELATING COMMITTEE. AGENDA January 21, 2016 NFPA, Quincy, MA

NATIONAL ELECTRICAL CODE CORRELATING COMMITTEE. AGENDA January 21, 2016 NFPA, Quincy, MA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NATIONAL ELECTRICAL CODE CORRELATING COMMITTEE AGENDA January 21, 2016

More information

American National Standard For Electrical Rigid Aluminum Conduit (ERAC)

American National Standard For Electrical Rigid Aluminum Conduit (ERAC) Revision of ANSI C80.5-1994 American National Standard For Electrical Rigid Aluminum Conduit (ERAC) Secretariat: Approved August 18, 2005 American National Standards Institute, Inc. NOTICE AND DISCLAIMER

More information

MATERIAL AND EQUIPMENT STANDARD FOR HOOKS, SHACKLES, EYE BOLTS AND CHAINS FIRST EDITION FEBRUARY 2005

MATERIAL AND EQUIPMENT STANDARD FOR HOOKS, SHACKLES, EYE BOLTS AND CHAINS FIRST EDITION FEBRUARY 2005 MATERIAL AND EQUIPMENT STANDARD FOR HOOKS, SHACKLES, EYE BOLTS AND CHAINS FIRST EDITION FEBRUARY 2005 This standard specification is reviewed and updated by the relevant technical committee on Apr. 2015.

More information

Connecticut Frequently Asked Questions

Connecticut Frequently Asked Questions Connecticut 2017 Frequently Asked Questions Disclaimer: This guide is designed for informational purposes only. It is not legal advice and is not intended to create an attorney-client relationship. The

More information

Tennessee Am I registered to vote?

Tennessee Am I registered to vote? Tennessee 2018 Disclaimer: This guide is designed for informational purposes only. It is not legal advice and is not intended to create an attorney-client relationship. The Election Protection Coalition

More information

National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-7070 www.nfpa.org Technical Committee on Emergency Communication Systems 2016 Second Draft

More information

Local elections. Referendum on the voting system used to elect MPs to the House of Commons

Local elections. Referendum on the voting system used to elect MPs to the House of Commons 5 MAY Local elections and Referendum on the voting system used to elect MPs to the House of Commons aboutmyvote.co.uk About this booklet On Thursday 5 May 2011, there will be a referendum on the voting

More information

TO ALL MEMBERS 1 FEBRUARY Dear Sirs AMENDMENT TO P&I, OFFSHORE AND DEFENCE RULES

TO ALL MEMBERS 1 FEBRUARY Dear Sirs AMENDMENT TO P&I, OFFSHORE AND DEFENCE RULES SETTING THE STANDARD FOR SERVICE AND SECURITY TO ALL MEMBERS 1 FEBRUARY 2010 Dear Sirs AMENDMENT TO P&I, OFFSHORE AND DEFENCE RULES This letter and attachments set out proposed amendments to the Association

More information

Enforcement and Compliance, International Trade Administration, Department of Commerce

Enforcement and Compliance, International Trade Administration, Department of Commerce This document is scheduled to be published in the Federal Register on 01/23/2018 and available online at https://federalregister.gov/d/2018-01146, and on FDsys.gov DEPARTMENT OF COMMERCE International

More information

OFFICE OF STATE HUMAN RESOURCES

OFFICE OF STATE HUMAN RESOURCES OFFICE OF STATE HUMAN RESOURCES NUMBER: HWP-1 TOTAL PAGES: 6 SUBJECT: Hot Work Program Effective Date: Revision Date: Revision #: RELATED LEGISLATION: This program outlines procedures for [Agency/University]

More information

ADOPTED REGULATION OF THE STATE ENVIRONMENTAL COMMISSION. LCB File No. R186-18

ADOPTED REGULATION OF THE STATE ENVIRONMENTAL COMMISSION. LCB File No. R186-18 ADOPTED REGULATION OF THE STATE ENVIRONMENTAL COMMISSION LCB File No. R186-18 EXPLANATION Matter in italics is new; matter in brackets [omitted material] is material to be omitted. AUTHORITY: 1, NRS 444.560;

More information

LIQUEFIED PETROLEUM GAS REGULATIONS 2012

LIQUEFIED PETROLEUM GAS REGULATIONS 2012 REPUBLIC OF RWANDA RWANDA UTILITIES REGULATORY AGENCY LIQUEFIED PETROLEUM GAS REGULATIONS 2012 SECTION ONE CITATION AND DEFINITIONS 1. Citation These Regulations may be cited as the Liquefied Petroleum

More information

SECTION DETENTION DOOR HARDWARE

SECTION DETENTION DOOR HARDWARE #C1305-0l SECTION 087163 - PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

M-Series, Actuator Overview. Machine Screw Cutaway. UNI-LIFT Machine Screw Actuators offer precise. 12

M-Series, Actuator Overview. Machine Screw Cutaway. UNI-LIFT Machine Screw Actuators offer precise. 12 M-, Actuator Overview UNI-LIFT Machine Screw Actuators offer precise positioning, uniform lifting speeds and capacity up to 250 tons. Standard model configurations include upright or inverted units with

More information

MINUTES OF MEETING. Technical Committee on Pulverized Fuel Systems

MINUTES OF MEETING. Technical Committee on Pulverized Fuel Systems MINUTES OF MEETING Technical Committee on Pulverized Fuel Systems January 7-8, 2014 Doubletree Hotel Orlando Airport Orlando, FL I. Attendance: Principal Members/Staff: Andy Smith, Technical Committee

More information

SOCIALIST REPUBLIC OF VIET NAM CONSTRUCTION. Independence - Freedom Happiness

SOCIALIST REPUBLIC OF VIET NAM CONSTRUCTION. Independence - Freedom Happiness THE MINISTRY OF SOCIALIST REPUBLIC OF VIET NAM CONSTRUCTION Independence - Freedom Happiness -------- ---------------- No.: 13/2013/TT-BXD Hanoi, August 15, 2013 CIRCULAR PRESCRIBING VERIFICATION, APPRAISAL

More information

LexisNexis (TM) New Jersey Annotated Statutes

LexisNexis (TM) New Jersey Annotated Statutes Page 1 21:1B-1. Definitions N.J. Stat. 21:1B-1 (2014) As used in this chapter: "Board" means the Liquefied Petroleum Gas Education and Safety Board; "Bulk plant" means intermediate establishments or points

More information

Corrigendum VOLUME I Table, Transport category 0, Column (2), Class 1

Corrigendum VOLUME I Table, Transport category 0, Column (2), Class 1 CORRIGENDUM Ref. Sales No. E.06.VIII.1 (ECE/TRANS/185, Vol. I and II) June 2007 New York and Geneva EUROPEAN AGREEMENT CONCERNING THE INTERNATIONAL CARRIAGE OF DANGEROUS GOODS BY ROAD (ADR) (applicable

More information

Municipal Election Procedures for the Alternate Voting Method Known as Vote by Mail and for the Use of Vote Tabulators

Municipal Election Procedures for the Alternate Voting Method Known as Vote by Mail and for the Use of Vote Tabulators Municipal Election Procedures for the Alternate Voting Method Known as Vote by Mail and for the Use of Vote Tabulators Purpose: To provide procedures for the alternate voting method known as Vote by Mail

More information

Invitation. to the Annual General Meeting 2014 on 20 May LeadIng.

Invitation. to the Annual General Meeting 2014 on 20 May LeadIng. Invitation to the Annual General Meeting 2014 on 20 May 2014 LeadIng. Invitation to the annual General Meeting of Linde aktiengesellschaft Dear Shareholders, You are invited to attend the Annual General

More information

Economic and Social Council

Economic and Social Council United Nations Economic and Social Council ECE/TRANS/WP.15/240/Corr.1 Distr.: General 6 June 2018 English Original: English and French Economic Commission for Europe Inland Transport Committee Working

More information

SUBCHAPTER 34C - CREMATORIES SECTION.0100 GENERAL PROVISIONS

SUBCHAPTER 34C - CREMATORIES SECTION.0100 GENERAL PROVISIONS SUBCHAPTER 34C - CREMATORIES SECTION.0100 GENERAL PROVISIONS 21 NCAC 34C.0101 ELECTION TO CREMATORY AUTHORITY (a) Definitions. As used in this Rule: (1) "Crematory operator" shall have the same meaning

More information

8. NFPA 5000 Second Draft (formerly ROC) Preparation. Public Comments to be distributed before meeting date.

8. NFPA 5000 Second Draft (formerly ROC) Preparation. Public Comments to be distributed before meeting date. AGENDA NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 SECOND DRAFT MEETING Thursday, May 23, 2013 DoubleTree by Hilton Hotel San Diego Downtown 1646 Front Street San Diego,

More information

2016 Bill. Second Session, 29th Legislature, 65 Elizabeth II THE LEGISLATIVE ASSEMBLY OF ALBERTA BILL 20 CLIMATE LEADERSHIP IMPLEMENTATION ACT

2016 Bill. Second Session, 29th Legislature, 65 Elizabeth II THE LEGISLATIVE ASSEMBLY OF ALBERTA BILL 20 CLIMATE LEADERSHIP IMPLEMENTATION ACT 2016 Bill Second Session, 29th Legislature, 65 Elizabeth II THE LEGISLATIVE ASSEMBLY OF ALBERTA BILL 20 CLIMATE LEADERSHIP IMPLEMENTATION ACT THE MINISTER OF ENVIRONMENT AND PARKS First Reading.......................................................

More information

February 5, 2010 CONFERENCE CALL. All USW District 2 Local Union Presidents and Recording Secretaries

February 5, 2010 CONFERENCE CALL. All USW District 2 Local Union Presidents and Recording Secretaries Michael Bolton Director, District 2 February 5, 2010 CONFERENCE CALL To: RE: All USW District 2 Local Union Presidents and Recording Secretaries 2010 USW District 2 Council Conference Dear Union Sisters

More information

Congressional Roll Call Votes on the Keystone XL Pipeline

Congressional Roll Call Votes on the Keystone XL Pipeline Congressional Roll s on the Keystone XL Pipeline Lynn J. Cunningham Information Research Specialist Beth Cook Information Research Specialist January 22, 2015 Congressional Research Service 7-5700 www.crs.gov

More information

Nominating Committee Process Last Updated 2/9/17

Nominating Committee Process Last Updated 2/9/17 Nominating Committee Process Last Updated 2/9/17 Governing document: By-Laws, Article V, Section 1 Nomination and Election of Directors Summary: Nominations are made by the Nominating Committee Nominating

More information

1 Batterymarch Park, Quincy, MA Phone: Fax: NATIONAL ELECTRICAL CODE CORRELATING COMMITTEE

1 Batterymarch Park, Quincy, MA Phone: Fax: NATIONAL ELECTRICAL CODE CORRELATING COMMITTEE National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NATIONAL ELECTRICAL CODE CORRELATING COMMITTEE AGENDA May 12-15, 2015

More information

WASTEWATER DISCHARGE PERMIT APPLICATION LAUNDRIES / LAUNDROMATS / DRY CLEANERS

WASTEWATER DISCHARGE PERMIT APPLICATION LAUNDRIES / LAUNDROMATS / DRY CLEANERS State of Rhode Island and Providence Plantations West Warwick Regional WASTEWATER TREATMENT FACILITY WEST WARWICK, RHODE ISLAND 02893 www.westwarwickri.org Bernard Bishop Superintendent Christine Suvajian

More information

Page 1 of Self-introduction of Committee Members and Guests. For a current committee roster, pg. 2.

Page 1 of Self-introduction of Committee Members and Guests. For a current committee roster, pg. 2. AGENDA NFPA Technical Committee on Structures and Construction & Materials NFPA 703 and NFPA 5000 Second Draft Meeting Tuesday, May 21, 2013 DoubleTree Hotel San Diego Downtown 1646 Front Street San Diego,

More information

Meeting Minutes. Attendees:

Meeting Minutes. Attendees: Meeting Minutes ISA 67 Alexander Drive P.O. Box 12277 Research Triangle Park, NC 27709 PHONE (919) 549-8411 FAX (919) 549-8288 E-MAIL info@isa.org www.isa.org Meeting: ISA77 Fossil Fuel Power Plant s Committee

More information

DECLARATORY STATEMENT. THIS CAUSE came on for consideration upon the Petition for Declaratory Statement

DECLARATORY STATEMENT. THIS CAUSE came on for consideration upon the Petition for Declaratory Statement ALEX SINK CHIEF FINANCIAL OFFICER STATE OF FLORIDA In The Matter Of: SPRING HILL FIRE RESCUE Case No.: 88055-07-FM Petition for Declaratory Statement / DECLARATORY STATEMENT THIS CAUSE came on for consideration

More information

An Urgent Bulletin from CSA Group

An Urgent Bulletin from CSA Group An Urgent Bulletin from CSA Group Gas Products No. 406 Effective Date: August 17, 2018 Date: February 13, 2017 Apply Before March 16, 2018 Announcing: Publication of CSA/ANSI NGV 2-2016 Compressed natural

More information

STANDARDS AND CERTIFICATION SECTOR OPERATION GUIDE

STANDARDS AND CERTIFICATION SECTOR OPERATION GUIDE STANDARDS AND CERTIFICATION SECTOR OPERATION GUIDE Rev. 1 August 26, 2005 Rev. 2 October 13, 2005 (editorially revised) Rev. 3 February 21, 2007 Rev. 4 June 13, 2007 Rev. 5 October 17, 2008 Rev. 6 November,

More information

University of Arizona AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION

University of Arizona AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION University of Arizona AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION The following provisions of the International Fire Code, 2012 Edition, as published by the International Code Council, Inc.

More information

Fire SCO Group C Level 2 Skill 1: Scene Examination

Fire SCO Group C Level 2 Skill 1: Scene Examination Candidate Name STANDARD: NFPA 1033, 2014 Edition, 4.2 Scene Examination: 4.2.1 to 4.2.9 Also see NFPA 921 Appendix A for forms, logs and notes templates to be used during investigation. Local department

More information

2. Introduction of committee members and guests. For a current committee roster, see page 2.

2. Introduction of committee members and guests. For a current committee roster, see page 2. AGENDA NFPA Technical Committee on Building Systems NFPA 5000 Second Draft Meeting Monday, June 20, 2016 Hilton Fort Lauderdale Marina Fort Lauderdale, FL 1. Call to order. Call meeting to order by Chair

More information

CHAPTER 9 FIRE PREVENTION** Article 1. Fire Prevention Code. Be it ordained by the City Council of the City of Wilburton as follows:

CHAPTER 9 FIRE PREVENTION** Article 1. Fire Prevention Code. Be it ordained by the City Council of the City of Wilburton as follows: CHAPTER 9 FIRE PREVENTION** Article 1. Fire Prevention Code Sec. 9-1. Fire Prevention Code. An Ordinance establishing minimum regulations governing the safeguarding the life and property from fire and

More information

CODES AND STANDARDS COMMITTEE OPERATING PROCEDURES

CODES AND STANDARDS COMMITTEE OPERATING PROCEDURES CODES AND STANDARDS COMMITTEE OPERATING PROCEDURES Table of Contents 1 Introduction... 1 2 Mission 1 3 Scope..1 4 Membership and Officers...3 5 Meetings and Quorum...3 6 NEMA Technical Position... 3 7

More information

TABLE OF CONTENTS. Jurisdiction and authority of commission. CHAPTER 1 PRELIMINARY PROVISIONS

TABLE OF CONTENTS. Jurisdiction and authority of commission. CHAPTER 1 PRELIMINARY PROVISIONS GAS AND HAZARDOUS LIQUIDS PIPELINES ACT - ENACTMENT Act of Dec. 22, 2011, P.L. 0, No. 127 Cl. 66 An Act Providing for gas and hazardous liquids pipelines and for powers and duties of the Pennsylvania Public

More information

Oklahoma Frequently Asked Questions TABLE OF CONTENTS

Oklahoma Frequently Asked Questions TABLE OF CONTENTS Oklahoma 2018 Frequently Asked Questions Disclaimer: This guide is designed for informational purposes only. It is not legal advice and is not intended to create an attorney-client relationship. The Election

More information

CLIMATE LEADERSHIP ACT

CLIMATE LEADERSHIP ACT Province of Alberta Statutes of Alberta, Current as of June 7, 2017 Office Consolidation Published by Alberta Queen s Printer Alberta Queen s Printer Suite 700, Park Plaza 10611-98 Avenue Edmonton, AB

More information

Lead Acid Battery Maintenance and Testing

Lead Acid Battery Maintenance and Testing 1 Lead Acid Battery Maintenance and Testing Moderator Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter: Rod Van

More information

The Ballot / Amendment Process

The Ballot / Amendment Process The Ballot / Amendment Process Brought to you by the Education Committee of IRP Hi my name is Ballot, B. N. Ballot Brand New Ballot Here are some questions you should be able to answer about the ballot

More information

adding a new Chapter 170, Fireworks and Pyrotechnics, which shall provide as follows:

adding a new Chapter 170, Fireworks and Pyrotechnics, which shall provide as follows: MUN11150571170510171 06. 15-17 TOWNSHIP OF WARWICK Lancaster County, Pennsylvania ORDINANCE NO. 279 AN ORDINANCE OF THE TOWNSHIP OF WARWICK, LANCASTER COUNTY, PENNSYLVANIA, TO AMEND THE CODE OF ORDINANCE

More information

Arizona Frequently Asked Questions

Arizona Frequently Asked Questions Disclaimer: This guide is designed for informational purposes only. It is not legal advice and is not intended to create an attorney-client relationship. The Election Protection Coalition does not warrant

More information

Connecticut Frequently Asked Questions

Connecticut Frequently Asked Questions Connecticut 2018 Frequently Asked Questions Disclaimer: This guide is designed for informational purposes only. It is not legal advice and is not intended to create an attorney-client relationship. The

More information

ARTICLES OF INCORPORATION

ARTICLES OF INCORPORATION ARTICLES OF INCORPORATION Enforced June 18, 2015 ITOCHU ENEX CO., LTD. ARTICLES OF INCORPORATION OF ITOCHU ENEX CO., LTD. CHAPTER I. GENERAL PROVISIONS Article 1. (Trade Name) The Company shall be called

More information

NIGERIAN ATOMIC ENERGY COMMISSION ACT

NIGERIAN ATOMIC ENERGY COMMISSION ACT NIGERIAN ATOMIC ENERGY COMMISSION ACT ARRANGEMENT OF SECTIONS 1. Establishment of the Nigerian Atomic Energy Commission. 2. Functions of the Commission. 3. Commission to act under directions. 4. Composition,

More information

CHAPTER 29: FIRE PREVENTION

CHAPTER 29: FIRE PREVENTION CHAPTER 29: FIRE PREVENTION 29.1 Applicability This Chapter shall provide the basic method for administration and enforcement of the State Fire Prevention Code in the Town of Camillus and shall establish

More information