1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M TO: NEC Code-Making Panel 1 FROM: Kimberly Shea, Administrator, Technical Projects DATE: April 3, 2015 SUBJECT: NFPA 70 First Draft TC Ballot Circulation (A2016) The April 1, 2015 date for receipt of the NEC First Draft Ballots has passed. The preliminary First Draft ballot results are shown on the attached report. 12 Members Eligible to Vote 0 Ballots Not Returned In accordance with the NFPA Regulations Governing the Development of NFPA Standards, attached are reasons for negative votes for review so you may change your ballot if you wish. Abstentions and affirmative comments are also included. Ballots received from alternate members are not included unless the ballot from the principal member was not received. If you wish to change your vote, the change must be received at NFPA on or before Friday, April 10, Members who have not returned a ballot may do so now. Changes must be submitted through the NFPA Vote.net Ballot site. The return of ballots is required by the Regulations Governing the Development of NFPA Standards.
2 FR 18, Global Input, See FR 18 FR 1, Section No. 90.2(A), See FR 1 Affirmative 9 Affirmative with Comment 1 Election NFPA 70 A16 This First revision should be revised to also include maintenance, testing and alteration. (A) Covered. This Code covers the installation, maintenance, alteration, testing, and removal of electrical conductors, equipment, and raceways; signaling and communications conductors, equipment, and raceways; and optical fiber cables and raceways for the following: Negative 2 While the Code covers the removal of wiring, these requirements are limited to only a few sections. The addition of "removal" to 90.2(A) may have unintended consequences and be misinterpreted to include more widespread removal of conductors, equipment and raceway than the sections specifically addressed. "Installation" is used in a broad sense and a laundry list of what aspects of installations the Code covers is not necessary. Kent A. Sayler NEC rules are primarily focused on electrical installations. Removal of electrical equipment is only required in a few specific sections therefore should not be included in 90.2(A). Removal of equipment that does not pose a hazard should not be covered by the NEC. 1 of 16
3 FR 2, Section No. 90.2(B), See FR 2 Affirmative 10 Negative 2 The term "energy storage" is not defined and therefore the breadth of this exclusion from the requirements of the NEC is unclear. In addition, the committee statement incorrectly states that "storage" was added when in fact "energy storage" was added. David L. Hittinger I am not in agreement that all "energy storage" should be exempt from the provisions in the NEC. Perhaps a definition would be an appropriate before excluding this from the NEC. FR 3, Section No. 90.3, See FR 3 FR 4, Section No. 90.8(B), See FR 4 2 of 16
4 FR 6, Article 100 [Excluding any Sub Sections], See FR 6 Affirmative 11 Affirmative with Comment 1 We are concerned that the proposed revisions are still not technically correct. For example, we wonder why there are definitions in part II that are used in 1,000 volt and less applications such a "fuse". It seems a number of these definitions are not unique to Part II. FR 8, Definition: Accessible, Readily (Readily Accessible)., See FR 8 Affirmative 10 Negative 2 Little to no justification was provided in the Committee statement for the change. Removal of the phrase "to whom ready access is requisite" is more than editorial in nature. Kent A. Sayler The panel statement does not cover all the changes made and their potential impacts. Removing the words "to those to whom ready access is requisite" was previously considered to permit equipment located behind locked doors to be considered readily accessible to qualified persons if they had the keys. Additionally the revised wording would prohibit locking doors or enclosures that limit access to any equipment that is required to be readily accessible such as panelboards in public spaces. Dictionaries indicate that a key is an instrument and an instrument is a tool. FR 9, Definition: Building., See FR 9 Affirmative 11 Affirmative with Comment 1 The Committee should have done more to improve the definition of "building" so that structures that stand alone, such as poles, are not considered buildings. 3 of 16
5 FR 10, Definition: Equipment., See FR 10 Affirmative 9 Negative 3 The addition of an Informational Note to the definition of "equipment" in order to provide additional examples to the existing laundry list of examples is not necessary. The definition already includes the phrase "and the like" to cover other examples. The proposed Informational Note adds no additional clarity to the existing examples and does not additionally clarify what is or what is not a structure. We are concerned that adding a laundry list in an informational note nearly as long as the laundry list already in the actual definition points to the fact that the definition is not correct. "And the like" seems to cover what is being prosed to be added as an informational note. Perhaps "such as" is more appropriate than "and the like". David L. Hittinger The added informational note adds a limited list of items that does not address mounting of AC equipment that FR 4732 was intended to correct. FR 13, Definition: Structure., See FR 13 Affirmative 10 Affirmative with Comment 2 David L. Hittinger We are concerned that the definition of equipment is unclear as indicated by the action on FR 10. We conclude that FR 13 will be difficult to apply as it may be unclear, vague and unenforceable. This revision does not correlate with revisions in FR 10 that adds a limited list of items in an informational note. FR 14, Definition: Voltage, Nominal., See FR 14 4 of 16
6 FR 31, Section No (A), See FR 31 Affirmative 9 Negative 3 The committee statement provides no substantiation for the change. The addition of this Informational Note may have unintended consequences and be misinterpreted to indicate that the Code is retroactive to reconditioned, refurbished and remanufacturered equipment. We conclude that "equipment" already includes the information in this FR. We further conclude that the action on FR 10 and the action of this FR adding an additional informational note raises concern that the definition of "equipment" is unclear. David L. Hittinger The definition of "equipment" does not include refurbished, remanufactured or reconditioned as described in the informational note. The definition may need to be revised if that is the intent. FR 39, Section No , See FR 39 FR 37, Section No , See FR 37 5 of 16
7 FR 35, Section No , See FR 35 FR 38, Section No [Excluding any Sub Sections], See FR 38 FR 41, Section No [Excluding any Sub Sections], See FR 41 FR 40, New Section after (C), See FR 40 Affirmative 10 Affirmative with Comment 1 Mohinder P. Sood This may be an enforcement issue for the AHJs as when inspectors go for inspections an electrician may or may not be present at the job site. Even when they have the proper tool, inspectors are not going to be present when actual work is being done (early morning, late night etc.). It will be the same issue when preventive maintenance is performed on the switchgear in large buildings. Negative 1 This change has the potential of having a significant impact on the electrical industry. Emphasis and priority should be given to properly torquing bolted connections before implementing mandatory requirements for smaller gauge wire and connections on terminal strips. 6 of 16
8 FR 55, Section No , See FR 55 Affirmative 7 Affirmative with Comment 3 This is a logical addition of installation requirements into an enforceable Code. Mohinder P. Sood David L. Hittinger Negative 2 Harry J. Sassaman Too many labels on any piece of equipment may not have the desired effect. It will also be an enforcement issue as the installers may not pay attention when they see so many labels. Correct the editorial error where the first strike through of "are" to "is' should be changed to "at". The second use of "is" was correct. NECA is mindful of the obligations to provide safe work environments for employees and understands requirements contained within both NFPA 70 National Electrical Code and NFPA 70E Standard for Electrical Safety in the Workplace. Section of the NEC is titled Arc Flash Hazard Warning. The information contained in this section should relate to a generic warning for qualified persons. As resolved by NEC CMP 1 in previous NEC development cycles, the warning should remain general in nature and should not include information about how to protect using PPE, because this section is not about how to protect. The NEC is an installation Code that provides information and requirements for electrical installations that essentially protect persons and property from hazards arising from use of electricity. It should not include workplace safety requirements related to how to protect against electric shock, arc flash and arc blast events that could occur when workers are performing energized work, justified or not justified. The label requirements proposed in FD 55 are currently addressed in NFPA 70E, as they should be. The proposed NEC revision would be inconsistent with the requirements in 70E and would introduce confusion for installers and inspectors, and would not be practical or enforceable. It also creates problems for manufacturers that current provide generic arc flash hazard warning labels at the factory, which is current provision in this section. The responsibility for this type of marking detail rests with owners, as indicated in NFPA 70E. With no date and time included in the proposed marking, there are serious concerns about the validity and accuracy of such information after the service equipment is initially marked. Another problem is that there are two clearing times (lines side of service OCPD and load side of service OCPD) upon which the values on such a mark or label should be based, further complicating the proposed marking requirement. NECA is also concerned that a false sense of security that might be created, and that the values of energy provided on such marks would not be accurate and compromise worker and owner safety. These proposed requirements appear to be beyond the NEC scope and should be provided only in NFPA 70E, and it is the responsibility of an owner to maintain their accuracy and validity. They should not become an installation requirement in the NEC. NECA emphasizes that compliance with NFPA 70E is a requirement, not an option. Roland E. Deike, Jr. EEI votes against the FR 55 revisions to , since these are prescriptive related practices already covered in NFPA 70E about incident energy, arc flash boundary, and PPE. Installation related requirements having dated provisions for markings similar to would be more appropriate for the NEC. 7 of 16
9 FR 42, Section No (A), See FR 42 Affirmative 9 Affirmative with Comment 1 Donald R. Iverson With the following sentence added as the second sentence of the Informational Note: Following the original equipment manufacture s guidance on permitted refurbishing and reconditioning activity is critical to the operational performance of the equipment. Negative 2 It appears the primary intent of this change is to provide traceability of refurbished or remanufactured equipment resold by 3rd parties and used to replace existing equipment. Providing company name and trademark labels on equipment that is regularly maintained and/or refurbished by the owner/operator as part of a regular equipment maintenance program does not enhance the traceability of the work. An industrial exemption should be included that states the following: "In industrial occupancies, where conditions of maintenance and supervision ensure that only qualfied persons service the equipment, the markings indicated in (B)are not required." Kent A. Sayler The proposed text creates an infeasible requirement for all reconditioned equipment to be marked, without defining what types of equipment maintenance, alterations, or adjustments constitute reconditioning. This is the user s responsibility to ensure the equipment as installed complies with all applicable requirements and is suitable for service FR 43, Section No (B), See FR 43 FR 44, Section No (C), See FR 44 Affirmative 11 Affirmative with Comment 1 We are concerned that this FR was made referencing a recommended practice that was not published at the time the Panel met. 8 of 16
10 FR 45, Section No (A), See FR 45 FR 46, Section No , See FR 46 FR 15, Section No (A), See FR 15 FR 17, Section No (B), See FR 17 Affirmative 11 Negative 1 Additional signage has not been shown to solve the stated problem. 9 of 16
11 FR 19, Section No (D), See FR 19 FR 20, Section No (E)(2), See FR 20 Affirmative 9 Affirmative with Comment 2 In is unclear what "structural overhangs" and "roof extensions" are. These appear to be vague and unenforceable. David L. Hittinger Negative 1 Michael A. Anthony Editorial: Change the wording in (2) (a) to the following. (a) Installation Requirements. Outdoor electrical equipment shall comply with (a)(1)(2) and (3) Although the cases will be rare, to convey the same interior working space conditions into exterior working space conditions is unwise in many campus power systems. FR 21, Section No (F), See FR 21 Affirmative 10 Negative 1 This requirement does not need to be carried over from (C). Suitable guarding of LV parts is already required in and addressed directly in (A). Relocating this requirement and creating an intermediate voltage level of V is redundant and may create confusion. This intermediate voltage does not exist in global standards, whith which the COde is attempting to correlate. The NEC should make a "clean distinction" that LV is < =1000V and HV is >1000V. Abstain 1 Michael A. Anthony In some cases, though not all, locked electrical closets present a new safety hazard. The difficulty will be most likely in existing facilities so some retroactive clauses would be helpful. New power systems should be designed with this safety condition up front. 10 of 16
12 FR 48, Section No (A), See FR 48 FR 49, Section No (C), See FR 49 Affirmative 11 Affirmative with Comment 1 FR 50, Section No , See FR 50 FR 52, Section No , See FR 52 We are concerned whether the FR incorporates the correct action word. As written, rooms with exposed live parts are to be marked with warning signs rather than signs with a different action word such as danger. 11 of 16
13 FR 32, Section No [Excluding any Sub Sections], See FR 32 FR 22, Section No (A) [Excluding any Sub Sections], See FR 22 FR 23, Section No (B)(1), See FR 23 FR 33, Section No (D), See FR 33 Affirmative 11 Affirmative with Comment 1 We recommend adding a definition of "unqualified person" to Article 100 or 110 to correlate with the addition of "unqualified person" in this FR. We propose the following definition from NFPA 70E: "Unqualified Person. A person who is not a qualified person." 12 of 16
14 FR 24, Section No (A)(2), See FR 24 Affirmative 10 Negative 2 We are concerned with "to ground" being removed without substantiation or explanation in the panel statement. David L. Hittinger The wording "to ground" was removed. FR 24 did not include this revision. FR 25, Section No (A), See FR 25 FR 26, Section No (B), See FR 26 FR 27, Section No (C), See FR of 16
15 FR 28, Section No (D), See FR 28 FR 34, Section No (E), See FR 34 FR 36, New Section after , See FR 36 Affirmative 10 Negative 2 The proposed new section is broad, overly restrictive and falls outside the scope of 90.1(A). There are many elements of a "complete electrical system design" that are not relevant to the practical safeguarding of persons and property from hazards arising from the use of electricity. The proposed text is also unenforceable. Is it the responsibility of the AHJ to review and approve "the complete electrical system design"? The new section also requires the "complete electrical system design" to be tested "when first installed on site". There are many tests conducted on electrical installations that are not relevant to practical safeguarding of persons and property. Also, testing installations "when first installed" may not be practical, or verify the safety of the installation, especially in the case of large projects that may take several years to install and energize. Michael A. Anthony I do not disagree that this kind of information is necessary for a ready to energize system but in many cases the as built condition of the wiring system is not available when the system is needed to continue construction. We should work on this language in the next stage so we retain the safety spirit of the PI without building in complicating inspection conditions for electrical contractors. 14 of 16
16 FR 30, Section No , See FR 30 FR 54, Section No , See FR 54 FR 11, Annex A, See FR 11 FR 47, Part II., See FR of 16
17 FR 7, Part II., See FR 7 FR 51, Part III., See FR 51 Affirmative 10 Affirmative with Comment 2 We are concerned that it is not clear that this FR is applicable to Part III of Article 110. David L. Hittinger There may be an error in the the committee statement that refers to Part!! and III. The action on FR 51 is for part III. See statement This revision from 600 Volts to 1000 volts correlates with first revision relative to Article 110 Parts II and III. FR 53, Part IV., See FR 53 FR 29, Part V., See FR 29 For Simple majority and also two third majority election; the simple affirmative votes needed are 7 and the two third affirmative votes needed are 8 16 of 16
Technical Committee on Electrical Equipment of Industrial Machinery (EEI-AAA)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Electrical Equipment of Industrial Machinery
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 16 FROM: Kimberly Shea,
More informationTechnical Committee on Electrical Equipment of Industrial Machinery (EEI-AAA)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Electrical Equipment of Industrial Machinery
More information6 Disagree (Drobnick, Dyson, Eblen, Gray, Mohla)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Electrical Safety in the Workplace
More informationMEMORANDUM. Subject: NEC Proposed Tentative Interim Amendment (TIA) No. 1117
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NEC Correlating Committee Kimberly Shea Date: August
More informationNATIONAL ELECTRICAL CODE CORRELATING COMMITTEE. AGENDA January 21, 2016 NFPA, Quincy, MA
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NATIONAL ELECTRICAL CODE CORRELATING COMMITTEE AGENDA January 21, 2016
More informationMEMORANDUM. SUBJECT: NFPA 70E Proposed Tentative Interim Amendment (TIA) No. 1253R
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: National Electrical Code Correlating Committee Sarah
More informationMEMORANDUM. Subject: NFPA 101 Proposed Tentative Interim Amendment (TIA) No.1114
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Correlating Committee on Safety to Life (SAF-AAC)
More informationAccording to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Air Conditioning (AIC-AAA) Allan Fraser,
More informationM E M O R A N D U M. NFPA 99 Second Draft Technical Committee FINAL Ballot Results (A2017 Cycle)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Electrical Systems
More informationMEMORANDUM. NFPA Technical Committee on Wastewater Treatment Plants. Subject: NFPA 820 Proposed Tentative Interim Amendment (TIA) No.
MEMORANDUM To: From: NFPA Technical Committee on Wastewater Treatment Plants Joanne Goyette Date: March 25, 2011 Subject: NFPA 820 Proposed Tentative Interim Amendment (TIA) No. 1025 The attached proposed
More information1 Batterymarch Park, Quincy, MA Phone: Fax: NATIONAL ELECTRICAL CODE CORRELATING COMMITTEE
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NATIONAL ELECTRICAL CODE CORRELATING COMMITTEE AGENDA May 12-15, 2015
More informationM E M O R A N D U M. NFPA Technical Committee on Explosion Protection Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Explosion Protection
More informationNational Fire Protection Association MEMORANDUM. Subject: NFPA 20 Proposed Tentative Interim Amendment (TIA) No. 1199
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Pumps Elena Carroll,
More informationMEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 9 From: Kimberly Shea, Project Administrator
More informationSupplemental Operating Procedures for the National Electrical Code Project
Adopted by the NEC Correlating Committee on April 27, 2012. Approved by the Standards Council on August 9, 2012. Introduction (a) Preamble. The Operations of the (i.e., the NEC Correlating Committee (CC)
More informationMEMORANDUM. Subject: NFPA 1917 Proposed Tentative Interim Amendment (TIA) No.1170
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Ambulances Yvonne Smith,
More informationNORTHERN IRELAND ELECTRICITY SAFETY RULES GUIDANCE DOCUMENT INSTRUCTION FOR OPERATIONS OR WORK ON THE PREMISES
ONCE PRINTED THIS IS AN UNCONTROLLED DOCUMENT NORTHERN IRELAND ELECTRICITY SAFETY RULES GUIDANCE DOCUMENT INSTRUCTION FOR OPERATIONS OR WORK ON THE PREMISES OF CUSTOMERS RECEIVING HIGH VOLTAGE SUPPLY SRG
More informationAnnex I To Loughborough University Estates Services Health and Safety Policy
Annex I Annex I To Loughborough University Estates Services Health and Safety Policy High Voltage Electricity System Safety Rules And Associated Safety Guidance 1. Introduction a. These Safety Rules are
More informationSUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: NEC Code-Making Panel 17 FROM: Kimberly Shea, Administrator, Technical
More informationJemena Electricity Networks
Total Document 2005 Edition Change Summary TXU AGL Electricy United Energy Distribution Office of the chief Electrical Inspector (ESV) SP AusNet Jemena Electricity Networks United Energy Energy Safe Victoria
More informationMEMORANDUM. NFPA Technical Committee on Liquefied Petroleum Gases. Subject: NFPA 58 Proposed Tentative Interim Amendment (TIA) No.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Liquefied Petroleum Gases
More informationNational Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-7070 www.nfpa.org Technical Committee on Emergency Communication Systems 2016 Second Draft
More information2015 Annual Revision Cycle Notice of a Consent Standard NFPA 1071
2015 Annual Revision Cycle Notice of a Consent Standard NFPA 1071 The Committee on Emergency Vehicle Technicians Professional Qualifications produced a First Revision Report for NFPA 1071, Standard for
More informationN.J.A.C. 5: NEW JERSEY ADMINISTRATIVE CODE Copyright (c) 2016 by the New Jersey Office of Administrative Law
N.J.A.C. 5:23-3.16 NEW JERSEY ADMINISTRATIVE CODE Copyright (c) 2016 by the New Jersey Office of Administrative Law *** This file includes all Regulations adopted and published through the *** *** New
More informationMEMORANDUM. NFPA Correlating Committee on Professional Qualifications. Subject: NFPA 1006 Proposed Tentative Interim Amendment (TIA) No.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Correlating Committee on Professional Qualifications
More informationORDINANCE NOW THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF MEADOWS PLACE, TEXAS:
ORDINANCE 2017-05 AN ORDINANCE OF THE CITY OF MEADOWS PLACE, TEXAS, REPEALING SUBSECTION 150.02(D) OF SECTION 150.02 OF CHAPTER 150 OF THE CODE OF ORDINANCES AND SUBSTITUTING A NEW SUBSECTION 150.02(D)
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Project
More informationExcerpts from 2011 City of Los Angeles Electrical Code and 2010 California Electrical Code (Based on 2008 National Electrical Code)
Excerpts from 2011 City of Los Angeles Electrical Code and 2010 California Electrical Code (Based on 2008 National Electrical Code) 2011 City of Los Angeles Electrical Code Excerpts: SEC. 93.0101. TITLE.
More informationMEMORANDUM. NFPA Technical Committee on Electronic Safety Equipment. Subject: NFPA 1982 Proposed Tentative Interim Amendment (TIA) No.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Electronic Safety Equipment
More informationCHAPTER 6 LINN COUNTY ELECTRICAL REGULATIONS TABLE OF CONTENTS
CHAPTER 6 LINN COUNTY ELECTRICAL REGULATIONS TABLE OF CONTENTS 6.1 ICC Electrical Code Administrative Provisions and National Electrical Code Adopted 6.2 Modification of the ICC Electrical Code Administrative
More informationFRCC REGIONAL RELIABILITY STANDARD DEVELOPMENT PROCESS MANUAL
FRCC REGIONAL RELIABILITY STANDARD DEVELOPMENT PROCESS MANUAL FRCC-RE-STD-001 Effective Date: March 3, 2017 Version: 1 3000 Bayport Drive, Suite 600 Tampa, Florida 33607-8410 (813) 289-5644 - Phone (813)
More informationTechnical Committee on Tank Leakage and Repair Safeguards. SUBJECT: NFPA 329 Second Draft TC Final Ballot Results (F2014)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Tank Leakage and Repair Safeguards Lawrence
More informationCP#28-05 Code Development
Code Development Approved: 09/24/05 Revised: 10/20/18 1.0 Introduction 1.1 Purpose of Council Policy: The purpose of this Council Policy is to prescribe the Rules of Procedure utilized in the continued
More informationMEMORANDUM. NFPA Correlating Committee on Health Care Facilities. Subject: NFPA 99 Proposed Tentative Interim Amendment (TIA) No.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Correlating Committee on Health Care Facilities
More informationCITY OF MELISSA, TEXAS
CITY OF MELISSA, TEXAS ORDINANCE NO. AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF MELISSA, TEXAS, AMENDING MELISSA S CODE OF ORDINANCES, ORDINANCE NO. 92-04, AS AMENDED, CHAPTER 12 (PLANNING AND ZONING),
More informationInterNational Electrical Testing Association Operating Principles and Procedures
InterNational Electrical Testing Association Operating Principles and Procedures 1. GENERAL These Operating Principles and Procedures describe the method used by the InterNational Electrical Testing Association
More informationJune Regulations Governing Consensus Development of the Water Efficiency and Sanitation Standard
June 2016 Regulations Governing Consensus Development of the Water Efficiency and Sanitation Standard TABLE OF CONTENTS SECTION 1.0 SCOPE... 1 SECTION 2.0 GENERAL... 1-2 SECTION 3.0 ORGANIZATION... 2-4
More informationORDINANCE # N:\WEB SITE UP DATE\Adoption of 2015 IBC_For Y Adoption_Final.docx Page 1 of 12
ORDINANCE #041317-02 AN ORDINANCE OF THE CITY OF SELMA AMENDING CHAPTER 66 OF THE CODE OF ORDINANCES AND ADOPTING THE 2015 EDITION OF THE INTERNATIONAL BUILDING CODE, REGULATING AND GOVERNING THE CONDITIONS
More informationMEMORANDUM. Subject: NFPA 259 Proposed Tentative Interim Amendment (TIA) No. 957
MEMORANDUM To: From: Technical Committee on Fire Tests Gregory Harrington, Acting Staff Liaison Date: May 12, 2009 Subject: NFPA 259 Proposed Tentative Interim Amendment (TIA) No. 957 The attached proposed
More informationTechnical Committee on Animal Housing Facilities. SUBJECT: NFPA 150 Second Draft TC Final Ballot Results (A2015)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Animal Housing Facilities Tracy Vecchiarelli,
More informationMEETING NOTICE 2014 NEC REPORT ON PROPOSALS
MEETING NOTICE 2014 NEC REPORT ON PROPOSALS JANUARY 9-21,2012 Important Information You Will Need for the Meetings in Hilton Head, SC Note from the Secretary Dear Panel Member: We are very pleased that
More informationApproved Revisions to UL s Accredited Procedures Effective November 1, 2009
Approved Revisions to UL s Accredited Procedures Effective November 1, 2009 Regulations Governing ANSI/UL Standards Technical Panels... 2 1 General Provisions... 2 2 Establishment and Operation of Standards
More informationElectricity Act, 1998 Loi de 1998 sur l électricité
Electricity Act, 1998 Loi de 1998 sur l électricité ONTARIO REGULATION 22/04 ELECTRICAL DISTRIBUTION SAFETY Consolidation Period: From October 1, 2017 to the e-laws currency date. Last amendment: O. Reg.
More informationFLORIDA BUILDING CODE
FLORIDA BUILDING CODE Sixth Edition (2017) Energy Conservation Item No. 5681L17 Florida Building Code, Energy Conservation, 6th Edition (2017) First Printing: July 2017 ISBN: 978-1-60983-695-5 COPYRIGHT
More informationMEMORANDUM. Subject: NFPA 1971 Proposed Tentative Interim Amendment (TIA) No.1159
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Correlating Committee on Fire and Emergency
More informationAPPENDIX K Chapter 27 of Florida Building Code, Building
APPENDIX K Chapter 27 of Florida Building Code, Building TABLE OF CONTENTS CHAPTER K1 SCOPE...................... 611 Section K101 General...611 K102 Applicability...611 CHAPTER K2 DEFINITIONS................
More informationAMERICAN IRON AND STEEL INSTITUTE PROCEDURES FOR ANSI-APPROVED STANDARDS FOR COLD-FORMED STEEL DESIGN AND CONSTRUCTION
AMERICAN IRON AND STEEL INSTITUTE PROCEDURES FOR ANSI-APPROVED STANDARDS FOR COLD-FORMED STEEL DESIGN AND CONSTRUCTION June 13, 2017 (Approved) American Iron & Steel Institute 25 Massachusetts Avenue,
More informationMINIMUM HOUSING STANDARDS ORDINANCE
MINIMUM HOUSING STANDARDS ORDINANCE FINDINGS AND AUTHORITY. Pursuant to G. S. 160-A-441, it is hereby declared that there exist in the planning jurisdiction of the Town of Pine Level, dwellings which are
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Liquefied Petroleum Gases
More informationTechnical Committee on Animal Housing Facilities
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Animal Housing Facilities Tracy Vecchiarelli,
More information2015 UPC & UMC TECHNICAL COMMITTEE MEETING WELCOME TECHNICAL COMMITTEE IAPMO CODES AND STANDARDS DEVELOPMENT PROCESS
2015 UPC & UMC TECHNICAL COMMITTEE MEETING WELCOME TECHNICAL COMMITTEE IAPMO CODES AND STANDARDS DEVELOPMENT PROCESS 2015-2018 1 THE STANDARDS DEVELOPMENT PROCESS STEP 1 PUBLIC AND COMMITTEE PROPOSAL STAGE
More informationCHAFFEE COUNTY ORDINANCE NO _
CHAFFEE COUNTY ORDINANCE NO. 2007-_ TITLE: AN ORDINANCE ADOPTING THE 2006 INTERNATIONAL BUILDING CODE, THE 2006 INTERNATIONAL RESIDENTIAL CODE, THE 2005 NATIONAL ELECTRIC CODE, 2006 INTERNATIONAL FUEL
More informationNORTH DAKOTA STATE ELECTRICAL BOARD MINUTES
NORTH DAKOTA STATE ELECTRICAL BOARD MINUTES Wednesday, January 22, 2014 The North Dakota State Electrical Board meeting was called to order at 8:30 a.m. by President Earl Scherer at the office of the North
More informationMEMORANDUM. Technical Committee on Liquefied Petroleum Gases. Subject: NFPA 58 Proposed Tentative Interim Amendment (TIA) No. 1153
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: Technical Committee on Liquefied Petroleum Gases
More informationPART 5 BUILDING REGULATIONS AND CODES CHAPTER 1 BUILDING CODES AND REGULATIONS CHAPTER 2 PLUMBING CODE
PART 5 BUILDING REGULATIONS AND CODES CHAPTER 1 BUILDING CODES AND REGULATIONS Section 5-101 Section 5-102 Section 5-103 Section 5-104 Section 5-105 Section 5-106 Building code adopted. Additions and changes
More informationElectricity Regulations 1947
Western Australia Electricity Act 1945 Electricity Regulations 1947 As at 01 Jan 2011 Version 05-c0-00 Western Australia Electricity Regulations 1947 CONTENTS Part I Preliminary 1. Citation 1 2. Terms
More informationACCREDITED STANDARDS COMMITTEE (ASC) Z540 OPERATING PROCEDURES 2016
ACCREDITED STANDARDS COMMITTEE (ASC) Z540 OPERATING PROCEDURES 2016 Accredited Standards Committee (ASC) procedure is used for the ASC Z540 Standards Committee. This version of the Accredited Standards
More informationComm 14 Technical/Substantive Changes Editions Department Action NFPA 1 Text Modified Comments
Global Overview. Clearinghouse Rule No.: 09-104 Comm 14 Technical/Substantive Changes 2008-2009 Editions Department Action NFPA 1 Text Modified Comments Statutes Interpreted. Sections 19.21 (4) (b); 101.02
More informationHot Work Procedures. Competent means possessing knowledge, experience and training to perform a specific duty.
Hot Work Procedures Purpose This procedure will provide the knowledge and equipment required to minimize the identified workplace hazards associated with Hot Work. These procedures will provide: information
More informationWHEREAS, copies of said Codes of Ordinances are available in the office of the City Secretary for review and inspection by the public.
Ordinance amending Corpus Christi Code of Ordinance, Chapter 14, Sections 14-201 &14-241 to adopt the National Electrical Code, 2017 Edition, with local amendments, amending sections 14-1306,14-1316, 14-1311,
More informationTackling Electrical System Efficiency, Safety and Reliability for pharmaceutical plants
Tackling Electrical System Efficiency, Safety and Reliability for pharmaceutical plants. MSD Rathdrum Site History 1961 Loftus Bryan Chemicals Ltd 1964 P1 Production Plant 1975 P2, QC / R&D & Pilot Plant
More informationCHAPTER 51: ELECTRICITY. General Provisions. Contractors. Inspections. Minimum Standards for Electrical Installations
CHAPTER 51: ELECTRICITY Section 51.01 Electrical work defined 51.02 Office of Electrical Inspector 51.03 Chapter application 51.04 Board of Examiners 51.05 Permits General Provisions Contractors 51.20
More informationRef No: N Date: May 25, 2005
Ref No: N05-045 Date: May 25, 2005 GAS PRODUCTS NO. 64 Effective Date: May 1, 2006 Call us today! We can help you stay on top of changes that will affect your Certification! 1-866-797-4272 Announcing:
More informationRESNA Policies and Procedures for the Development of RESNA Assistive Technology Standards February 17, 2016
RESNA Policies and Procedures for the Development of RESNA Assistive Technology Standards February 17, 2016 Copyright by the Rehabilitation Engineering and Assistive Technology Society of North America
More informationIEEE POWER ENGINEERING SOCIETY TECHNICAL COUNCIL ORGANIZATION AND PROCEDURES MANUAL. Revision: July 2003
IEEE POWER ENGINEERING SOCIETY TECHNICAL COUNCIL ORGANIZATION AND PROCEDURES MANUAL Revision: July 2003 IEEE POWER ENGINEERING SOCIETY TECHNICAL COUNCIL ORGANIZATION AND PROCEDURES MANUAL Table of Contents
More informationHas Decreed. Article 2 This decision shall be published in the Official Gazette and shall be enforced as of the next day of publication.
Decree of The Minister of Trade and Industry No. ( ) of 2006 On the Enactment of the Executive Regulations of the Consumer Protection Law Issued By Law (67) of 2006 Minister of Trade and Industry After
More informationSUB-ANALYSIS. Title CONSTRUCTION LICENSING, PERMITS AND REGULATION
SUB-ANALYSIS Title CHAPTER 4 CONSTRUCTION LICENSING, PERMITS AND REGULATION Section 4.01 Building Code Subd. 1 Subd. 2 Subd. 3 Subd. 4 Codes Adopted by Reference Application, Administration and Enforcement
More informationPROCEDURES AND GUIDELINES FOR APPLYING SERVICE CONNECTION AT 11 KV / 33 KV HIGH TENSION (HT) & 132 KV EXTRA HIGH TENSION (EHT)
PROCEDURES AND GUIDELINES FOR APPLYING SERVICE CONNECTION AT 11 KV / 33 KV HIGH TENSION (HT) & 132 KV EXTRA HIGH TENSION (EHT) Note. The procedures and guidelines mentioned herein are in accordance with
More informationFormal Interpretations/ Interprétation formelle
Formal Interpretations/ Interprétation formelle This section lists questions that individuals have submitted about a particular standard. Each question has been reviewed and answered by the appropriate
More informationLegal Obligations in Construction Contracts Concluded by Employers Operating in Egypt
Legal Obligations in Construction Contracts Concluded by Employers Operating in Egypt Copyright 2015, L&E Global We set out below important legal information that applies to all companies and entities
More informationElectricity (Consumer Safety) Regulation 2006
New South Wales Electricity (Consumer Safety) Regulation 2006 under the Electricity (Consumer Safety) Act 2004 Her Excellency the Governor, with the advice of the Executive Council, has made the following
More informationCITY OF MUSKEGO CHAPTER 15 - ELECTRICAL CODE (Ord. # )
CITY OF MUSKEGO CHAPTER 15 - ELECTRICAL CODE (Ord. #935-07-03-97) 15.01 OBJECT AND PURPOSE... 1 15.02 SCOPE... 1 15.021 APPLICABILITY... 1 15.025 CODE ADOPTED... 2 15.03 ENFORCEMENT... 2 15.04 INTERPRETATIONS...
More informationCITY OF HOUSTON ELECTRICAL CODE ADMINISTRATIVE CODE PROVISIONS for the NATIONAL ELECTRICAL CODE. Adopted by Ord. No. 2017
CITY OF HOUSTON ELECTRICAL CODE 2017 ADMINISTRATIVE CODE PROVISIONS for the NATIONAL ELECTRICAL CODE Adopted by Ord. No. 2017 Effective September 1, 2017 2017 Houston Electrical Code CONTENTS Page Chapter
More informationAreas that have been designed and constructed for performing open-flame or spark-producing work.
PURPOSE Baylor University recognizes that there is a potential for injury to people and damage to property that can result from fire or sparks that arise when hot work is performed outside of a designated
More informationSTATE OF FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF FLORIDA CONDOMINIUMS, TIMESHARES AND MOBILE HOMES
STATE OF FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF FLORIDA CONDOMINIUMS, TIMESHARES AND MOBILE HOMES IN RE: PETITION FOR ARBITRATION Townhouses at Bonnie Bay Condominium Association,
More informationHOT WORK MANAGEMENT PROGRAM
HOT WORK MANAGEMENT PROGRAM Rose-Hulman Institute of Technology Table of Contents SECTION 1.0 Purpose 2.0 Regulatory Reference 3.0 Scope 4.0 Elements of the Program 5.0 Responsibility 6.0 Training and
More informationThe Development and Revision of FSC Normative Documents FSC-PRO V3-1 EN
The Development and Revision of FSC Normative Documents Title: Document reference code: Approval: Contact for comments: The Development and Revision of FSC Normative Documents V3-0: FSC BOARD OF DIRECTORS,
More informationUniversity of Arizona AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION
University of Arizona AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION The following provisions of the International Fire Code, 2012 Edition, as published by the International Code Council, Inc.
More informationCHAPTER 4 FOOD LICENSING AND REGULATIONS. Article I Food Licensing and Regulations
CHAPTER 4 FOOD LICENSING AND REGULATIONS Article I Food Licensing and Regulations 4.101 4.107 ARTICLE I FOOD LICENSING AND REGULATIONS Section 4.101 Adoption of the FDA 2009 Food Code That a certain document,
More informationFENCE PERMIT APPLICATION
36725 Division Road P.O. Box 457 Richmond MI 48062 (586) 727-7571 ext. 202 (586) 727-2489 fax FENCE PERMIT APPLICATION Property Address: Parcel Number: Oct. 2015 APPLICATION FOR FENCE CITY OF RICHMOND
More informationAccredited Standards Committee Z136 for the Safe Use of Lasers. Procedures for the Development of Z136 American National Standards
Accredited Standards Committee Z136 for the Safe Use of Lasers Procedures for the Development of Z136 American National Standards ANSI approved May 10, 2013 ASC Z136 approved April 18, 2013 Table of Contents
More informationORDINANCE NO. WHEREAS, Ordinances No and were approved by the Los Angeles City Council and became on effective December 30, 2016;
ORDINANCE NO. An ordinance amending Articles 1, 1.2, 3, 4, 5 and 9 of Chapter IX of the Los Angeles to fix technical and referencing errors discovered after adoption of the tri-annual building code amendment
More informationHOT WORK PROGRAM OSHA
HOT WORK PROGRAM 1910.252 OSHA Table of Contents Purpose... 3 Definitions... 3 Responsibilities... 3 Hot Work Permitted Locations... 5 Fire Prevention Precautions... 5 Personal Protective Equipment...
More informationORDINANCE NO DISPLAY REQUIREMENTS; ESTABLISHING A PERMIT tp :::z: APPLICATION; ESTABLISHING PERMIT PROCEDURES;;:..
." ORDINANCE NO. 92-02 ~ AN ORDINANCE TO BE ENTITLED THE HERNAND~ COUNTY FIREWORKS ORDINANCE; PROVIDING FOR~ - e-) SHORT TITLE; PROVIDING FOR DEFINITIONS; ~ PROVIDING FOR APPLICABILITY; PROHIBITING THE~
More informationNIGERIAN ELECTRICITY REGULATORY COMMISSION REGULATIONS FOR EMBEDDED GENERATION 2012
NIGERIAN ELECTRICITY REGULATORY COMMISSION REGULATIONS FOR EMBEDDED GENERATION 2012 1 P a g e REGULATION NO: 0112 NIGERIAN ELECTRICITY REGULATORY COMMISSION In exercise of its powers to make Regulations
More informationCONSULTATIVE COUNCIL CONSENSUS PROCEDURES. General. This consensus process shall be followed by the Consultative Council (Council) and its committees.
CONSULTATIVE COUNCIL CONSENSUS PROCEDURES Section 1. Section 2. General. This consensus process shall be followed by the Consultative Council (Council) and its committees. Definitions. 2.1 "Appointed members"
More informationThe Safety of Employees (Electricity) Ordinance, 1956.
OF THE STATES (Made on the 18th April, 1956.) The Safety of Employees (Electricity) Ordinance, 1956. ARRANGEMENT OF SECTIONS 201 (No. XII- 1956) PART I Interpretation I. Interpretation. PART II Safety
More informationANSI Essential Requirements: Due process requirements for American National Standards
ANSI Essential Requirements: Due process requirements for American National Standards Edition: January 2008 Editorial Correction to 3.1: March 11, 2008 Copyright by the American National Standards Institute
More informationORDINANCE NO BE IT FURTHER ENACTED AND ORDAINED by the Mayor and City Council of Laurel, Maryland that
ORDINANCE NO. 1932 AN ORDINANCE OF THE MAYOR AND CITY COUNCIL OF LAUREL, MD TO AMEND THE CITY OF LAUREL UNIFIED LAND DEVELOPMENT CODE; CHAPTER 20, LAND DEVELOPMENT AND SUBDIVISION, TO ADD ARTICLE VIA,
More informationReceive FREE updates, excerpts of code references, technical articles, and more when you register your code book. Go to
A MEMBER OF THE INTERNATIONAL CODE FAMILY IZC INTERNATIONAL ZONING CODE Receive FREE updates, excerpts of code references, technical articles, and more when you register your code book. Go to www.iccsafe.org/codesplus
More informationINTERNATIONAL LABOUR CONFERENCE
INTERNATIONAL LABOUR CONFERENCE Convention 184 CONVENTION CONCERNING SAFETY AND HEALTH IN AGRICULTURE The General Conference of the International Labour Organization, Having been convened at Geneva by
More informationUNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. NORTH AMERICAN ELECTRIC ) Docket No. RR RELIABILITY CORPORATION )
UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION NORTH AMERICAN ELECTRIC ) Docket No. RR06-1-000 RELIABILITY CORPORATION ) QUARTERLY REPORT OF THE NORTH AMERICAN ELECTRIC RELIABILITY
More informationRISKTOPICS. DISCUSSION For the purposes of this document, hot work: Management practices: Hot work Property and Business Interruption January 2013
RISKTOPICS Management practices: Hot work Property and Business Interruption January 2013 This document highlights the property conservation responsibilities of those who utilize hot work outside of areas
More informationTitle 30: Public Service
Title 30: Public Service Chapter 86: Vermont Underground Utility Damage Prevention System 7001. Definitions In this chapter: (1) "Board" means the public service board. (2) "Company" means any public utility
More informationHYDRO AND ELECTRIC ENERGY ACT
Province of Alberta HYDRO AND ELECTRIC ENERGY ACT Revised Statutes of Alberta 2000 Chapter H-16 Current as of March 31, 2017 Office Consolidation Published by Alberta Queen s Printer Alberta Queen s Printer
More information(Published in the Topeka Metro News October 7, 2013) ORDINANCE NO
1 2 3 4 5 6 7 8 9 10 11 12 (Published in the Topeka Metro News October 7, 2013) ORDINANCE NO. 19856 AN ORDINANCE introduced by City Manager Jim Colson, granting to Westar Energy, Inc., an electric franchise
More informationRegulations Governing Consensus Development of the Uniform Solar, Hydronics & Geothermal and Swimming Pool, Spa & Hot Tub Codes
Regulations Governing Consensus Development of the Uniform Solar, Hydronics & Geothermal and Swimming Pool, Spa & Hot Tub Codes Revised Feb 2018 TABLE OF CONTENTS SECTION 1.0 SCOPE... 1 SECTION 2.0 GENERAL...
More informationSUMMARY OF CHANGES IN ISO 9001:2008 (DRAFT INTERNATIONAL STANDARD)
SUMMARY OF CHANGES IN ISO 9001:2008 (DRAFT INTERNATIONAL STANDARD) Disclaimer This update on the ISO 9001:2008 amendment is based on the Draft International Standard (DIS) published in September 2007.
More informationProcessing of Building Consent Applications
G05 Processing of Building Consent Applications Contents 1. INTRODUCTION... 1 2. MANAGING PROCESSING TIMES... 2 3. LINKAGE WITH RMA PROCESSES... 2 4. INITIAL ASSESSMENT BY CONSENTS OFFICER... 3 5. ASSESS
More information