National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: NEC Code-Making Panel 17 FROM: Kimberly Shea, Administrator, Technical Projects DATE: January 25, 2016 SUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. The attached report shows the number of affirmative, negative and abstaining votes as well as the explanation of the vote for each revision. To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2 /3 of ballots returned. See Sections 3.3.4.3 (c) and 4.3.10.1 of the Regulations Governing the Development of NFPA Standards. NEC Panel 17 Final Ballot Results - Page 1 of 53-01/28/16
of 2 1/25/2016 12:11 PM Second Revision No. 7509-NFPA 70-2015 [ Section No. 425.6 ] 425.6 Listed Equipment. Fixed industrial process heating equipment and motors shall be considered continuous loads listed and labeled. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Dec 14 15:29:39 EST 2015 Committee Statement Committee Statement: Response Message: During the first draft transcription for FR 4841, a typographical (cut and paste) error resulted in an error of proposed section 425.6. That is evident based on the combination of the section title, resulting text, and the proposed text from PI 879. Ballot Results This item has passed ballot 13 Eligible Voters 0 Not Returned 12 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Shell, Kenneth M. NEC Panel 17 Final Ballot Results - Page 2 of 53-01/28/16
of 2 1/25/2016 12:11 PM Swim, Peter C. Williams, Matt B. Yasenchak, Randy J. Abstention Hamilton, III, E. P. Voting restricted to 680 NEC Panel 17 Final Ballot Results - Page 3 of 53-01/28/16
of 50 1/28/2016 2:35 PM Second Revision No. 4801-NFPA 70-2015 [ Section No. 422.6 ] 422.6 Listing Required. All appliances operating at 50 volts or more shall be listed. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 13:56:05 EST 2015 Committee Statement Committee Statement: Response Message: The Panel recognized the need to be more specific as to which appliances should be listed. Applied the code required protection from contact with live parts (Section 110.27) as the means to specify which appliance shall be listed. Public Comment No. 1517-NFPA 70-2015 [Section No. 422.6] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 10 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter NEC Panel 17 Final Ballot Results - Page 4 of 53-01/28/16
of 50 1/28/2016 2:35 PM Williams, Matt B. Yasenchak, Randy J. Negative with Comment Cook, Donald R. While I agree that listing of some appliances may not be necessary to achieve protection from shock and fire, I don't agree with using a 50 volt line of demarcation. I would recommend relief be provided by an exception. See the following recommended text for 422.6. 422.6 Listing Required. All appliances shall be listed. Exception: Appliances supplied or charged by a listed Class 2 power source. NEC Panel 17 Final Ballot Results - Page 5 of 53-01/28/16
of 50 1/28/2016 2:35 PM Second Revision No. 4802-NFPA 70-2015 [ Section No. 422.15(A) ] (A) Listed and labeled central vacuum outlet assemblies shall be permitted to be connected to a branch circuit in accordance with 210.23(A). Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 14:32:44 EST 2015 Committee Statement Committee Statement: Response Message: The Panel agrees with public comment clarifying certain equipment be listed and labeled instead of just listed. Listing agencies do not consider a product to be listed unless the label has actually been applied. Public Comment No. 1250-NFPA 70-2015 [Section No. 422.15(A)] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 10 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter NEC Panel 17 Final Ballot Results - Page 6 of 53-01/28/16
of 50 1/28/2016 2:35 PM Williams, Matt B. Yasenchak, Randy J. Affirmative with Comment Cook, Donald R. While always supportive of listing and generally supportive of labeling of listed products, it is obvious that many variables impact labeling of different products throughout the NEC. The CC approach to have a task group review this issue across the NEC is likely the best approach to ensure practical and uniform application of this concept. NEC Panel 17 Final Ballot Results - Page 7 of 53-01/28/16
of 50 1/28/2016 2:35 PM Second Revision No. 4803-NFPA 70-2015 [ Section No. 422.16(B)(1) ] (1) Electrically Operated In-Sink Waste Disposers. Electrically operated in-sink waste disposers shall be permitted to be cord-and-plug-connected with a flexible cord identified as suitable in the installation instructions of the appliance manufacturer where all of the following conditions are met: (1) The flexible cord shall be terminated with a grounding-type attachment plug. Exception: A listed in-sink waste disposer distinctly marked to identify it as protected by a system of double insulation, or its equivalent, shall not be required to be terminated with a grounding-type attachment plug. (2) The length of the cord shall not be less than 450 mm (18 in.) and not over 900 mm (36 in.). (3) Receptacles shall be located to protect against physical damage to the flexible cord. (4) The receptacle shall be accessible. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 14:49:32 EST 2015 Committee Statement Committee Statement: Response Message: In the context of a sink waste disposer, it is unclear in the exception what the equivalent to double insulation is. Since these appliances may either be protected by grounding or double insulation, the or its equivalent statement in the requirement could be deleted without affecting product design and to also avoid confusion. Public Comment No. 941-NFPA 70-2015 [Section No. 422.16(B)(1)] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 11 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All NEC Panel 17 Final Ballot Results - Page 8 of 53-01/28/16
of 50 1/28/2016 2:35 PM Blewitt, Thomas V. Cook, Donald R. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter Williams, Matt B. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 9 of 53-01/28/16
of 50 1/28/2016 2:35 PM Second Revision No. 4804-NFPA 70-2015 [ Section No. 422.16(B)(2) ] (2) Built-in Dishwashers and Trash Compactors. Built-in dishwashers and trash compactors shall be permitted to be cord-and-plug-connected with a flexible cord identified as suitable for the purpose in the installation instructions of the appliance manufacturer where all of the following conditions are met: (1) The flexible cord shall be terminated with a grounding-type attachment plug. Exception: A listed dishwasher or trash compactor distinctly marked to identify it as protected by a system of double insulation, or its equivalent, shall not be required to be terminated with a grounding-type attachment plug. (2) For a trash compactor, the length of the cord shall be 0.9 m to 1.2 m (3 ft to 4 ft) measured from the face of the attachment plug to the plane of the rear of the appliance. (3) For a built-in dishwasher, the length of the cord shall be 0.9 m to 2.0 m (3 ft to 6.5 ft) measured from the face of the attachment plug to the plane of the rear of the appliance. (4) Receptacles shall be located to protect against physical damage to the flexible cord. (5) The receptacle for a trash compactor shall be located in the space occupied by the appliance or adjacent thereto. (6) The receptacle for a built-in dishwasher shall be located in the space adjacent to the space occupied by the dishwasher. (7) The receptacle shall be accessible. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 14:58:41 EST 2015 Committee Statement Committee Statement: Response Message: In the context of dishwashers or trash compactors, it is unclear in the exception what the equivalent to double insulation is. Since these appliances may either be protected by grounding or double insulation, the or its equivalent statement in the requirement could be deleted without affecting product design and to also avoid confusion. Public Comment No. 942-NFPA 70-2015 [Section No. 422.16(B)(2)] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned NEC Panel 17 Final Ballot Results - Page 10 of 53-01/28/16
of 50 1/28/2016 2:35 PM 11 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter Williams, Matt B. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 11 of 53-01/28/16
of 50 1/28/2016 2:35 PM Second Revision No. 4805-NFPA 70-2015 [ Section No. 422.16(B)(4) ] (4) Range Hoods. Range hoods shall be permitted to be cord-and-plug-connected with a flexible cord identified as suitable for use on range hoods in the installation instructions of the appliance manufacturer, where all of the following conditions are met: (1) The flexible cord is terminated with a grounding-type attachment plug. Exception: A listed range hood distinctly marked to identify it as protected by a system of double insulation, or its equivalent, shall not be required to be terminated with a grounding-type attachment plug. (2) The length of the cord is not less than 450 mm (18 in.) and not over 1.2 m (4 ft). (3) Receptacles are located to protect against physical damage to the flexible cord. (4) The receptacle is accessible. (5) The receptacle is supplied by an individual branch circuit. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 15:02:22 EST 2015 Committee Statement Committee Statement: Response Message: In the context of range hoods it is unclear in the exception what the equivalent to double insulation is. Since these appliances may either be protected by grounding or double insulation, the or its equivalent statement in the requirement could be deleted without affecting product design and to also avoid confusion. Public Comment No. 944-NFPA 70-2015 [Section No. 422.16(B)(4)] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 11 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention NEC Panel 17 Final Ballot Results - Page 12 of 53-01/28/16
0 of 50 1/28/2016 2:35 PM Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter Williams, Matt B. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 13 of 53-01/28/16
1 of 50 1/28/2016 2:35 PM Second Revision No. 4806-NFPA 70-2015 [ Section No. 422.18 ] 422.18 Support of Ceiling-Suspended (Paddle) Fans. Ceiling-suspended (paddle) fans shall be supported independently of an outlet box or by one of the following: (1) A listed outlet box or listed outlet box systems system identified for the use and installed in accordance with 314.27(C). (2) A listed outlet box system, a listed locking support and mounting receptacle, and a compatible factory installed attachment fitting designed for support, identified for the use and installed in accordance with 314.27(E) Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 16:17:08 EST 2015 Committee Statement Committee Statement: Response Message: The Panel agrees to adding reference to the listed device and compatible factory installed attachment fitting noting that this is predicated on Panel 9 retaining its complementary First Revision (the new 314.27(E)). Made editorial revisions for clarity. Public Comment No. 662-NFPA 70-2015 [Section No. 422.18] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 11 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal NEC Panel 17 Final Ballot Results - Page 14 of 53-01/28/16
2 of 50 1/28/2016 2:35 PM Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter Williams, Matt B. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 15 of 53-01/28/16
3 of 50 1/28/2016 2:35 PM Second Revision No. 4807-NFPA 70-2015 [ Section No. 422.33 ] 422.33 Disconnection of Cord-and-Plug-Connected or Attachment Fitting Connected Appliances. (A) Separable Connector or an Attachment Plug (or Attachment Fitting) and Receptacle. For cord-and-plug-(or attachment fitting ) connected appliances, an accessible separable connector or an accessible plug (or attachment fitting) and receptacle combination shall be permitted to serve as the disconnecting means. The attachment fitting shall be a factory installed part of the appliance and suitable for disconnection of the appliance. Where the separable connector or plug (or attachment fitting) and receptacle combination are not accessible, cord-and-plug-connected or attachment fitting-and-plugconnected appliances shall be provided with disconnecting means in accordance with 422.31. (B) Connection at the Rear Base of a Range. For cord-and-plug-connected household electric ranges, an attachment plug and receptacle connection at the rear base of a range, accessible from the front by removal of a drawer, shall meet the intent of 422.33(A). (C) Rating. The rating of a receptacle or of a separable connector shall not be less than the rating of any appliance connected thereto. Exception: Demand factors authorized elsewhere in this Code shall be permitted to be applied to the rating of a receptacle or of a separable connector. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 17:04:29 EST 2015 Committee Statement Committee Statement: Response Message: The Panel added reference to attachment fitting as a means of disconnect. Because the attachment fitting must be suitable for the purpose of disconnection, the proposal was amended accordingly. Public Comment No. 663-NFPA 70-2015 [Section No. 422.33] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 11 Affirmative All 0 Affirmative with Comments NEC Panel 17 Final Ballot Results - Page 16 of 53-01/28/16
4 of 50 1/28/2016 2:35 PM 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter Williams, Matt B. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 17 of 53-01/28/16
5 of 50 1/28/2016 2:35 PM Second Revision No. 4808-NFPA 70-2015 [ Section No. 422.50 ] 422.50 Cord-and-Plug-Connected Pipe Heating Assemblies. Cord-and-plug-connected pipe heating assemblies intended to prevent freezing of piping shall be listed and labeled. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 17:32:20 EST 2015 Committee Statement Committee Statement: Response Message: The Panel agrees with public comment clarifying certain equipment be listed and labeled instead of just listed. Listing agencies do not consider a product to be listed unless the label has actually been applied. Public Comment No. 1251-NFPA 70-2015 [Section No. 422.50] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 10 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter NEC Panel 17 Final Ballot Results - Page 18 of 53-01/28/16
6 of 50 1/28/2016 2:35 PM Williams, Matt B. Yasenchak, Randy J. Affirmative with Comment Cook, Donald R. While always supportive of listing and generally supportive of labeling of listed products, it is obvious that many variables impact labeling of different products throughout the NEC. The CC approach to have a task group review this issue across the NEC is likely the best approach to ensure practical and uniform application of this concept. NEC Panel 17 Final Ballot Results - Page 19 of 53-01/28/16
7 of 50 1/28/2016 2:35 PM Second Revision No. 4809-NFPA 70-2015 [ Section No. 424.39 ] 424.39 Clearance from Other Objects and Openings. Heating elements of cables installed in ceilings shall be separated at least 200 mm (8 in.) from the edge of outlet boxes and junction boxes that are to be used for mounting surface luminaires. A clearance of not less than 50 mm (2 in.) shall be provided from recessed luminaires and their trims, ventilating openings, and other such openings in room surfaces. No heating cable shall be covered by any surface-mounted equipment. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 17:50:40 EST 2015 Committee Statement Committee Statement: As amended in the First Revision, the requirement no longer distinguishes between the heating and non-heating conductors of heating cables. The non-heating conductors are unnecessarily being required to be separated 8 in. from surface luminaire outlet and junction boxes and 2 in from recessed luminaires, their trim and ventilating openings. Such conductors are arguably no different from other current carrying conductors that are not similarly restricted in their location. Response Message: Public Comment No. 945-NFPA 70-2015 [Section No. 424.39] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 11 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal Jhonson, Don W. NEC Panel 17 Final Ballot Results - Page 20 of 53-01/28/16
8 of 50 1/28/2016 2:35 PM Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter Williams, Matt B. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 21 of 53-01/28/16
9 of 50 1/28/2016 2:35 PM Second Revision No. 4810-NFPA 70-2015 [ Section No. 424.66(B) ] (B) Limited Access. Where the enclosure is located in a space above a ceiling, all of the following shall apply: (1) The enclosure shall be accessible through a lay-in-type ceiling or an access panel(s). (2) The width of the working space shall be the width of the enclosure or a minimum of 762 mm (30 in.), whichever is greater. (3) All doors or hinged panels shall open to at least 90 degrees. (4) The space in front of the enclosure shall comply with the depth requirements of Table 110.26(A)(1). a. A horizontal ceiling T-bar and associated lay-in ceiling tiles shall be permitted in this space. b. The work working space shall be otherwise unobstructed to the floor by permanently installed fixtures such as cabinets, walls, or partitions. Informational Note: For additional installation information, see NFPA 90A-2015, Standard for the Installation of Air-Conditioning and Ventilating Systems, and NFPA 90B-2015, Standard for the Installation of Warm Air Heating and Air-Conditioning Systems. Supplemental Information File Name 424.66_B_SR-4810_DJG.docx Description Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 17:58:59 EST 2015 Committee Statement Committee Statement: As currently written this section would prohibit the occupant of the building from installing movable items such as tables or desks in the space beneath the ceiling. Also revised text for clarification. The Panel would like CMP-1 to address the revisions to this requirement. Response Message: Public Comment No. 777-NFPA 70-2015 [Section No. 424.66(B)] Ballot Results This item has passed ballot NEC Panel 17 Final Ballot Results - Page 22 of 53-01/28/16
0 of 50 1/28/2016 2:35 PM 11 Eligible Voters 0 Not Returned 11 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter C. Williams, Matt B. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 23 of 53-01/28/16
1 of 50 1/28/2016 2:35 PM Second Revision No. 4811-NFPA 70-2015 [ Section No. 424.92(D) ] (D) Labels Provided by Manufacturer. The manufacturers of heating panels or heating panel sets shall provide marking labels that indicate that the space-heating installation incorporates heating panels or heating panel sets and instructions that the labels shall be affixed to the panelboards to identify which branch circuits supply the circuits to those space-heating installations. If the heating panels and heating panel set installations are visible and distinguishable after installation, the labels shall not be required to be provided and affixed to the panelboards. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 18:26:55 EST 2015 Committee Statement Committee Statement: Response Message: Circuit identification is already adequately addressed by 408.4(A) which requires all circuits and circuit modifications to be marked at the panelboard by a suitable method determined by the installer and accepted by an AHJ. There is no direction as to the size, shape, color or placement of the label, just that the label be affixed to the panelboard and identify the branch circuit(s). The manufacturersupplied label rule only applies to heating panels and heating panel sets but not to heating cables. The electrician can provide a more complete description of the location of the heating panel. Public Comment No. 1623-NFPA 70-2015 [Section No. 424.92(D)] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 11 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal NEC Panel 17 Final Ballot Results - Page 24 of 53-01/28/16
2 of 50 1/28/2016 2:35 PM Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter C. Williams, Matt B. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 25 of 53-01/28/16
3 of 50 1/28/2016 2:35 PM Second Revision No. 4812-NFPA 70-2015 [ Section No. 424.99(B)(5) ] (5) Fault GFCI Protection. A device to open all ungrounded conductors Branch circuits supplying the heating panels panel or heating panel sets, provided by the manufacturer, shall function when a low- or high-resistance line-to-line, line-to-grounded conductor, or line-to-ground fault occurs, such as the result of a penetration of the element or element assembly shall have ground-fault circuit-interrupter protection for personnel. (6) Grounding Braid or Sheath. Excluding nonheating leads, grounding means, such as copper braid, metal sheath, or other approved means, shall be provided with or as an integral part of the heating panel or heating panel set. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 18:36:11 EST 2015 Committee Statement Committee Statement: Response Message: The requirements are being simplified to be clear that a GFCI shall be provided in all cases. Public Comment No. 1612-NFPA 70-2015 [Sections 424.99(B)(5), 424.99(B)(6)] Ballot Results This item has passed ballot 11 Eligible Voters 0 Not Returned 11 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. NEC Panel 17 Final Ballot Results - Page 26 of 53-01/28/16
4 of 50 1/28/2016 2:35 PM Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Swim, Peter C. Williams, Matt B. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 27 of 53-01/28/16
5 of 50 1/28/2016 2:35 PM Second Revision No. 4813-NFPA 70-2015 [ Section No. 425.1 ] 425.1 Scope. This article covers fixed industrial process heating employing electric resistance or electrode heating technology. For the purpose of this article, heating equipment shall include boilers, electrode boilers, duct heaters, strip heaters, immersion heaters, process air heaters, or other approved fixed electric equipment used for industrial process heating. This article shall not apply to heating and room air conditioning for personnel spaces covered by Article 424, fixed heating equipment for pipelines and vessels covered by Article 427, and induction and dielectric heating equipment covered by Article 665, and industrial furnaces incorporating silicon carbide, molybdenum, or graphite process heating elements. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 19:05:16 EST 2015 Committee Statement Committee Statement: Response Message: The Panel has been informed there is technical complexity to these heating elements not currently being recognized by overcurrent protection requirements in Article 425. Relevant NFPA standards that this article may apply to: NFPA 86, Standard for Ovens and Furnaces; NFPA 79 Electrical Standard for Industrial Machinery. Public Comment No. 422-NFPA 70-2015 [Section No. 425.1] Ballot Results This item has passed ballot 9 Eligible Voters 0 Not Returned 9 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Cook, Donald R. Hunter, Randal NEC Panel 17 Final Ballot Results - Page 28 of 53-01/28/16
6 of 50 1/28/2016 2:35 PM Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 29 of 53-01/28/16
7 of 50 1/28/2016 2:35 PM Second Revision No. 4814-NFPA 70-2015 [ Section No. 426.54 ] 426.54 Cord-and-Plug-Connected Deicing and Snow-Melting Equipment. Cord-and-plug-connected deicing and snow-melting equipment shall be listed and labeled. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Nov 02 19:25:58 EST 2015 Committee Statement Committee Statement: Response Message: The Panel agrees with public comment clarifying certain equipment be listed and labeled instead of just listed. Listing agencies do not consider a product to be listed unless the label has actually been applied. Public Comment No. 1252-NFPA 70-2015 [Section No. 426.54] Ballot Results This item has passed ballot 10 Eligible Voters 0 Not Returned 9 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Shell, Kenneth M. NEC Panel 17 Final Ballot Results - Page 30 of 53-01/28/16
8 of 50 1/28/2016 2:35 PM Yasenchak, Randy J. Affirmative with Comment Cook, Donald R. While always supportive of listing and generally supportive of labeling of listed products, it is obvious that many variables impact labeling of different products throughout the NEC. The CC approach to have a task group review this issue across the NEC is likely the best approach to ensure practical and uniform application of this concept. NEC Panel 17 Final Ballot Results - Page 31 of 53-01/28/16
9 of 50 1/28/2016 2:35 PM Second Revision No. 4815-NFPA 70-2015 [ Section No. 680.4 ] 680.4 Approval of Equipment. All electrical equipment installed in the water, walls, or decks of pools, fountains, and similar installations shall comply with the provisions of this article. Equipment and products shall be listed and labeled. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Nov 03 11:03:35 EST 2015 Committee Statement Committee Statement: Response Message: The text listed alone would allow for listed units that would require the Inspection Authority to search in various databases of the certification agencies while conducting inspection in the field. This is inconvenient and sometimes difficult. The text and labeled was added as this would mandate a certification (listing) mark on the product or its smallest unit container for small components such as wire connectors. The text for swimming pool use was not added to this section as it would then apply to all electrical products used in the Article. This would include conduit, wire connectors and grounding and bonding equipment that are not listed for swimming pool use. Text such as identified for swimming pool and spa use would be appropriate in other sections of the Article. Public Comment No. 1089-NFPA 70-2015 [Section No. 680.4] Ballot Results This item has passed ballot 10 Eligible Voters 0 Not Returned 9 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Hamilton, III, E. P. Hunter, Randal Jhonson, Don W. NEC Panel 17 Final Ballot Results - Page 32 of 53-01/28/16
0 of 50 1/28/2016 2:35 PM Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Yasenchak, Randy J. Affirmative with Comment Cook, Donald R. While always supportive of listing and generally supportive of labeling of listed products, it is obvious that many variables impact labeling of different products throughout the NEC. The CC approach to have a task group review this issue across the NEC is likely the best approach to ensure practical and uniform application of this concept. NEC Panel 17 Final Ballot Results - Page 33 of 53-01/28/16
1 of 50 1/28/2016 2:35 PM Second Revision No. 4816-NFPA 70-2015 [ Section No. 680.7 ] 680.7 Grounding and Bonding Terminals. Grounding and bonding terminals shall be identified for use in wet and corrosive environments. Fieldinstalled grounding and bonding connections in a damp, wet, or corrosive environment shall be composed of copper, copper alloy, or stainless steel. They shall be listed and labeled for direct burial use. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Nov 03 11:05:58 EST 2015 Committee Statement Committee Statement: Response Message: The requirements for grounding and bonding equipment in UL 467 do not at present have an option of a rating wet or corrosive environments. Requirements in UL 467 for a rating of direct burial would mandate materials that have proven resistant to the corrosive environments around swimming pool equipment: stainless steel, copper and high copper content copper alloys. The text or concrete encasement is not necessary as the marking for the listed terminal would be direct burial or DB. The text and labeled was added as this would mandate a certification (listing) mark on the product or its smallest unit container for small components such as wire connectors. The text listed alone would allow for listed units that would require the Inspection Authority to search in various databases of the certification agencies while conducting inspection in the field. This is inconvenient and sometimes difficult. Public Comment No. 1098-NFPA 70-2015 [Section No. 680.7] Ballot Results This item has passed ballot 10 Eligible Voters 0 Not Returned 9 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Hamilton, III, E. P. NEC Panel 17 Final Ballot Results - Page 34 of 53-01/28/16
2 of 50 1/28/2016 2:35 PM Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Yasenchak, Randy J. Affirmative with Comment Cook, Donald R. While always supportive of listing and generally supportive of labeling of listed products, it is obvious that many variables impact labeling of different products throughout the NEC. The CC approach to have a task group review this issue across the NEC is likely the best approach to ensure practical and uniform application of this concept. NEC Panel 17 Final Ballot Results - Page 35 of 53-01/28/16
3 of 50 1/28/2016 2:35 PM Second Revision No. 4817-NFPA 70-2015 [ New Section after 680.13 ] 680.14 Corrosive Environment. (A) General. Areas where pool sanitation chemicals are stored; areas with circulation pumps, automatic chlorinators, and filters; open areas under decks adjacent to or abutting the pool structure; and the like shall be considered to be a corrosive environment. The air in such areas shall be considered to be laden with acid, chlorine, and/or bromine vapors, and any liquids or condensation in those areas shall be considered to be laden with acids, chlorine, and/or bromine. (B) Wiring Methods. Wiring methods in the areas described in 680.14(A) shall be listed, labeled, and identified for use in such areas. Rigid metal conduit, intermediate metal conduit, rigid polyvinyl chloride conduit, and reinforced thermosetting resin conduit are considered to be resistant to the corrosive environment specified in 680.14(A). Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Nov 03 11:08:59 EST 2015 Committee Statement Committee Statement: Response Message: The topic of suitability to physical damage should be separate text. The reference to specific wiring methods should be deleted from the Article. Wiring methods that have been specifically evaluated for the type of corrosive environment around swimming pool pumps and sanitation chemicals are not as yet readily available. A new Section 680.14 should be created to detail the corrosion resistance necessary of wiring methods needed in swimming pool installations. Ballot Results This item has passed ballot 10 Eligible Voters 0 Not Returned 10 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All NEC Panel 17 Final Ballot Results - Page 36 of 53-01/28/16
4 of 50 1/28/2016 2:35 PM Blewitt, Thomas V. Cook, Donald R. Hamilton, III, E. P. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Yasenchak, Randy J. NEC Panel 17 Final Ballot Results - Page 37 of 53-01/28/16
5 of 50 1/28/2016 2:35 PM Second Revision No. 4818-NFPA 70-2015 [ Section No. 680.21(A)(1) ] (1) General. Where branch circuits for pool-associated motors are subject to physical damage and/or installed in wet, damp, or corrosive environments, that portion of the branch circuit shall be installed in rigid metal conduit, intermediate metal conduit, rigid polyvinyl chloride conduit, reinforced thermosetting resin conduit, or Type MC cable, suitable for the conditions subject to Wiring methods installed in the corrosive environment described in 680.14 shall comply with 680.14(B) or shall be type MC cable listed and labeled for that location. Wiring methods installed in these locations shall contain an insulated copper equipment grounding conductor sized in accordance with Table 250.122 but not smaller than 12 AWG. Where installed in dry, noncorrosive environments, branch circuits shall comply with the general requirements in Chapter 3. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Nov 03 11:43:29 EST 2015 Committee Statement Committee Statement: Wiring methods that have been specifically evaluated for the type of corrosive environment around swimming pool pumps and sanitation chemicals are not as yet readily available. Made revisions to correlate with new Section 680.14. The wiring methods have had acceptable field history in swimming pool installations. The First Draft text referencing resistance to physical damage is not necessary as it applies to all wiring methods. Response Message: Public Comment No. 732-NFPA 70-2015 [Section No. 680.21(A)(1)] Ballot Results This item has passed ballot 10 Eligible Voters 0 Not Returned 9 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. NEC Panel 17 Final Ballot Results - Page 38 of 53-01/28/16
6 of 50 1/28/2016 2:35 PM Hamilton, III, E. P. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Yasenchak, Randy J. Affirmative with Comment Cook, Donald R. While always supportive of listing and generally supportive of labeling of listed products, it is obvious that many variables impact labeling of different products throughout the NEC. The CC approach to have a task group review this issue across the NEC is likely the best approach to ensure practical and uniform application of this concept. NEC Panel 17 Final Ballot Results - Page 39 of 53-01/28/16
7 of 50 1/28/2016 2:35 PM Second Revision No. 4819-NFPA 70-2015 [ Section No. 680.22(B)(7) ] (7) Low-Voltage Gas-Fired Electronic Luminaires Luminaires, Decorative Fireplaces, Fire Pits, and Similar Equipment. Listed and labeled low-voltage gas-fired-electronically ignited luminaires and outdoor luminaire lighting appliances with luminaires, decorative fireplaces, fire pits, and similar equipment using low-voltage ignitors that do not require grounding, that do not exceed the low-voltage contact limit, and that and are supplied by listed and labeled transformers or power supplies that comply with 680.23(A)(2)with outputs that do not exceed the low-voltage contact limit shall be permitted to be located less than 1.5 m (5 ft) from the inside walls of the pool. Metallic luminaires and outdoor luminaire lighting appliances equipment shall be bonded in accordance with the requirements in 680.26(B). Transformers or power supplies supplying these luminaires and outdoor lluminaire lighting appliances this type of equipment shall be installed in accordance with the requirements in 680.24. Metallic gas piping shall be bonded in accordance with the requirements in 250.104(B) and 680.26(B)(7). Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Nov 03 12:35:43 EST 2015 Committee Statement Committee Statement: Clarification of the meaning of outdoor luminated lighting appliances is required. This type of equipment includes gas-fired fireplaces, fire pits and similar equipment. In addition, clarification is needed that it is the equipment power supply that is low voltage. The text and labeled was added to replicate similar changes made by the Panel. Response Message: Public Comment No. 947-NFPA 70-2015 [Section No. 680.22(B)(7)] Ballot Results This item has passed ballot 10 Eligible Voters 0 Not Returned 8 Affirmative All 2 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All NEC Panel 17 Final Ballot Results - Page 40 of 53-01/28/16
8 of 50 1/28/2016 2:35 PM Blewitt, Thomas V. Hunter, Randal Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Yasenchak, Randy J. Affirmative with Comment Cook, Donald R. While always supportive of listing and generally supportive of labeling of listed products, it is obvious that many variables impact labeling of different products throughout the NEC. The CC approach to have a task group review this issue across the NEC is likely the best approach to ensure practical and uniform application of this concept. Hamilton, III, E. P. This is a necessary addition to the Code which is intended to eliminate confusion as to how these devices are addressed. NEC Panel 17 Final Ballot Results - Page 41 of 53-01/28/16
9 of 50 1/28/2016 2:35 PM Second Revision No. 4820-NFPA 70-2015 [ Section No. 680.23(A)(2) ] (2) Transformers and Power Supplies. Transformers and power supplies used for the supply of underwater luminaires, together with the transformer or power supply enclosure, shall be listed, labeled, and identified for swimming pool and spa use. The transformer or power supply shall incorporate either a transformer of the isolated winding type, with an ungrounded secondary that has a grounded metal barrier between the primary and secondary windings, or one that incorporates an approved system of double insulation between the primary and secondary windings. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Nov 03 12:39:21 EST 2015 Committee Statement Committee Statement: Response Message: The text listed alone would allow for listed units that would require the Inspection Authority to search in various databases of the certification agencies while conducting inspection in the field. This is inconvenient and sometimes difficult. The text and labeled was added as this would mandate a certification (listing) mark on the product. The additional text and identified accurately reflects the Definitions in Chapter 1. It is appropriate in this instance as there are Listed and Labeled transformers readily available that are not intended for swimming pool installations. Public Comment No. 1302-NFPA 70-2015 [Section No. 680.23(A)(2)] Ballot Results This item has passed ballot 10 Eligible Voters 0 Not Returned 9 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. Hamilton, III, E. P. Hunter, Randal NEC Panel 17 Final Ballot Results - Page 42 of 53-01/28/16
0 of 50 1/28/2016 2:35 PM Jhonson, Don W. Krepps, Rachel E. Querry, Dennis Michael Sandberg, Chester L. Schapp, Ronald F. Yasenchak, Randy J. Affirmative with Comment Cook, Donald R. While always supportive of listing and generally supportive of labeling of listed products, it is obvious that many variables impact labeling of different products throughout the NEC. The CC approach to have a task group review this issue across the NEC is likely the best approach to ensure practical and uniform application of this concept. NEC Panel 17 Final Ballot Results - Page 43 of 53-01/28/16
1 of 50 1/28/2016 2:35 PM Second Revision No. 4828-NFPA 70-2015 [ Section No. 680.23(F)(1) ] (1) Wiring Methods. Where branch-circuit wiring on the supply side of enclosures and junction boxes connected to conduits run to underwater luminaires are subject to physical damage and/or are is installed in wet, damp, or corrosive environments as described in 680.14, the wiring method of that portion of the branch circuit shall be installed using rigid metal conduit, intermediate metal conduit, as required in 680.14(B) or shall be liquidtight flexible nonmetallic conduit, rigid polyvinyl chloride conduit, or reinforced thermosetting resin conduit suitable for the location. Where installed in dry, noncorrosive environments, branch circuits shall comply with the general requirements in Chapter 3. Wiring methods installed in wet, damp, or corrosive environments as described in 680.14 shall contain an insulated copper equipment grounding conductor sized in accordance with Table 250.122, but not less smaller than 12 AWG shall be required. Where installed in noncorrosive environments, branch circuits shall comply with the general requirements in Chapter 3. Exception: Where connecting to transformers for pool lights, liquidtight flexible metal conduit shall be permitted. The length shall not exceed 1.8 m (6 ft) for any one length or exceed 3.0 m (10 ft) in total length used. Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Nov 03 13:37:38 EST 2015 Committee Statement Committee Statement: A modification required due to the creation of 680.14. Response Message: Ballot Results This item has passed ballot 10 Eligible Voters 0 Not Returned 5 Affirmative All 5 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Hunter, Randal NEC Panel 17 Final Ballot Results - Page 44 of 53-01/28/16
2 of 50 1/28/2016 2:35 PM Jhonson, Don W. Sandberg, Chester L. Schapp, Ronald F. Yasenchak, Randy J. Affirmative with Comment Blewitt, Thomas V. In conjunction with this SR, we request that the Technical Correlating Committee also consider making an editorial change by adding the phrase or power supply to the Exception after the word transformers. Panel 17 has modified 680 consistently to add or power supply to references involving transformers for low voltage pool lighting in order to address the new solid-state low voltage lighting technologies that may utilize a power supply instead of simply a transformer. See 680.22(B)(6), 680.23(A)(1), 680.23(A)(2) and 680.22(B)(7). Cook, Donald R. While not included in this SR, a correlation item could be added to the exception to revise transformers to transformers and power supplies to correlate with other text in 680.23 (A) Hamilton, III, E. P. In conjunction with this SR, I am requesting that the Technical Correlating Committee also consider making an editorial change by adding the phrase or power supply to the Exception after the word transformers. Panel 17 has modified 680 consistently to add or power supply to references involving transformers for low voltage pool lighting in order to address the new solid-state low voltage lighting technologies that may utilize a power supply instead of simply a transformer. At the end of the CMP-17 SR meeting last November, it was noticed that the change had not been made in this section, and it should be made in order to provide consistency in the addressing of pool lights; the exception as currently written deals specifically with transformers serving low voltage pool lights, so the inclusion of power supplies in the exception will be consistent with other current language addressing these lights. I am requesting that the Technical Correlating Committee address this specific section and consider making the suggested editorial change to correlate and preserve consistency with the remainder of the references to these devices in 680. Krepps, Rachel E. In conjunction with SR-4828, we request that the Technical Correlating Committee consider an editorial change to add the phrase or power supply after the word "transformers" in the Exception. Panel 17 has consistently modified Article 680 to include power supplies in references involving transformers for low voltage pool lighting in order to address new solid-state low voltage lighting technologies utilize a power supply instead of a transformer. Querry, Dennis Michael In conjunction with this SR, I am requesting that the Technical Correlating Committee also consider making an editorial change by adding the phrase or power supply to the Exception after the word transformers. Panel 17 has modified 680 consistently to add or power supply to references involving transformers for low voltage pool lighting in order to address the new solid-state low voltage lighting technologies that may utilize a power supply instead of simply a transformer. At the end of the CMP-17 SR meeting last November, it was noticed that the change had not been made in this section, and it should be made in order to provide consistency in the addressing of pool lights; the exception as currently written deals specifically with transformers serving low voltage pool lights, so the inclusion of power supplies in the exception will be consistent with other current language addressing these lights. I am requesting that the Technical Correlating Committee address this specific section and consider making the suggested editorial change to correlate and preserve consistency with the remainder of the references to these devices in 680 NEC Panel 17 Final Ballot Results - Page 45 of 53-01/28/16
3 of 50 1/28/2016 2:35 PM Second Revision No. 4821-NFPA 70-2015 [ Section No. 680.24(A)(1) ] (1) Construction. The junction box shall be listed, labeled, and identified as a swimming pool junction box and shall comply with the following conditions: (1) Be equipped with threaded entries or hubs or a nonmetallic hub (2) Be comprised of copper, brass, suitable plastic, or other approved corrosion-resistant material (3) Be provided with electrical continuity between every connected metal conduit and the grounding terminals by means of copper, brass, or other approved corrosion-resistant metal that is integral with the box Submitter Information Verification Submitter Full Name: CMP 17 Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Nov 03 12:50:25 EST 2015 Committee Statement Committee Statement: Response Message: The text listed alone would allow for listed units that would require the Inspection Authority to search in various databases of the certification agencies while conducting inspection in the field. This is inconvenient and sometimes difficult. The text and labeled was added as this would mandate a certification (listing) mark on the product. The additional text and identified accurately reflects the Definitions in Chapter 1. It is appropriate in this instance as there are Listed and Labeled equipment readily available that are not intended for swimming pool installations. Public Comment No. 1303-NFPA 70-2015 [Section No. 680.24(A)(1)] Ballot Results This item has passed ballot 10 Eligible Voters 0 Not Returned 9 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Affirmative All Blewitt, Thomas V. NEC Panel 17 Final Ballot Results - Page 46 of 53-01/28/16