FINAL. New York State Reliability Council (NYSRC) Reliability Rules Subcommittee (RRS) Minutes of Meeting #17

Similar documents
FINAL. New York State Reliability Council (NYSRC) Reliability Rules Subcommittee (RRS) Minutes of Meeting #19

FINAL. New York State Reliability Council (NYSRC) Reliability Rules Subcommittee (RRS) Minutes of Meeting #14

FINAL. New York State Reliability Council (NYSRC) Reliability Rules Subcommittee (RRS) Minutes of Meeting #21

FINAL. New York State Reliability Council, L.L.C. (NYSRC) Reliability Rules Subcommittee (RRS) Minutes of Meeting #40

Meeting of the New York State Reliability Council, L.L.C. (NYSRC) Reliability Rules Subcommittee (RRS)

Final Minutes of RRS Meeting # 157

Couch White, LLP (Large Customers Sector) Member - Vice Chair Consolidated Edison Co. of NY, Inc. Alternate Member

New York Independent System Operator (NYISO)*

DRAFT. Summary Minutes and Highlights

Members and Alternates In Attendance: Unaffiliated Member EC Chair, RRS Chair, RCMS Chair Consolidated Edison Co. of NY, Inc. Member, Vice Chair

Wholesale Seller s Sector; Independent Power Producers of NY. New York Independent Systems Operator (NYISO)* LeBoeuf Lamb Greene & MacRae (LLG&M)

Others: Electric Power Resources, LLC RRS Chairman National Grid, USA RCMS Chairman. New York Independent System Operator (NYISO)

Randy Bower New York Independent System Operator (NYISO)*

NYISO Agreements. New York Independent System Operator, Inc. Document Generated On: 3/5/2013

Motion in Opposition to Grid s Appeal to the Management Committee

130 FERC 61,151 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER INITIATING REVIEW OF NOTICE OF PENALTY. (Issued February 26, 2010)

Re: Errata Filing for Joint Submittal of Motion for Leave to Respond and Response to Indicated LSEs Comments, Docket No. ER09-40S-000.

DRAFT. August 12, :05 a.m. 12:30 p.m.

California Independent System Operator Corporation Fifth Replacement Tariff

Reliability Standards Development Procedures

Nominating Committee Report

NIGERIAN ELECTRICITY REGULATORY COMMISSION REGULATIONS FOR EMBEDDED GENERATION 2012

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

Request for Proposal To Provide Southern Tri-Valley Area Transmission Expansion Alternatives To California Independent System Operator Corporation

UNITED STATES OF AMERICA 82 ferc 61, 223 FEDERAL ENERGY REGULATORY COMMISSION

Meeting Minutes GADSTF Event Subgroup Conference Call

152 FERC 61,060 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER ON TECHNICAL CONFERENCE. (Issued July 20, 2015)

Service Agreement No. under PG&E FERC Electric Tariff Volume No. 5

DRAFT R E S O L U T I O N. Resolution E Registration Process for Community Choice Aggregators.

CONSOLIDATED TRANSMISSION OWNERS AGREEMENT. RATE SCHEDULE FERC No. 42

Rules of Procedure. Effective: May 4, 2016

June 14, Please contact the undersigned if you have any questions concerning this filing.

Minutes Operating Reliability Subcommittee

Notes Disturbance Monitoring SDT Project

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. NORTH AMERICAN ELECTRIC ) Docket No. RR RELIABILITY CORPORATION )

FOR CONSIDERATION. May 23, The Board of Trustees. Thomas Falcone

Compliance and Certification Committee Charter

Policy Requirements and Preliminary Results

Meeting Notes Project 2016-EPR-02 August 11, 2016

ORDER NO In this Order, the Public Service Commission ( Commission ) finds that Potomac

SERC Regional Standards Development Procedure Exhibit C to the Amended and Restated Regional Entity Delegation Agreement between

Millennium Pipeline Company, L.L.C. 6 th Annual Customer Meeting October 14, Joe Shields President

North American Electric Reliability Corporation (NERC) Rules of Procedure Effective in Manitoba April 1, 2012

Yours truly, Mark Seibert, Manager, NYISO Member Relations 10 Krey Blvd Rensselaer, New York 12144

New York State Assembly Carl E. Heastie Speaker. Committee on. Energy. Amy R. Paulin Chair

MINUTES OF THE REGULAR MEETING OF THE ENGINEERING AND OPERATIONS COMMITTEE OF THE RANCHO CALIFORNIA WATER DISTRICT Thursday, April 29, :30 a.m.

Calendar Year 2014 PacifiCorp News Feed OASIS Postings

Alberta Electric System Operator

MARKET PARTICIPANT SERVICE AGREEMENT. This MARKET PARTICIPANT SERVICE AGREEMENT is dated this day of, 2013 and is entered into by and between:

Midwest Reliability Organization

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. NORTH AMERICAN ELECTRIC ) Docket No. RR RELIABILITY CORPORATION )

EDB Information Disclosure Requirements Information Templates for Schedules 11a 13

Insulation Life Subcommittee - Unapproved Meeting Minutes November 2, 2011 Boston, MA

Meeting Notes Project Disturbance Monitoring Standard Drafting Team April 16-19, 2013

PARTICIPANTS AGREEMENT. among. ISO New England Inc. as the Regional Transmission Organization for New England. and. the New England Power Pool.

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

Texas Reliability Entity Standards Development Process

EVERSeURCE. ~Ri\1~ ~-~4~O. August 21, 2015

165 FERC 61,016 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER ACCEPTING TARIFF REVISIONS. (Issued October 12, 2018)

Reliability Must-run Settlement Agreement Among California ISO, Northern California Power Agency and Pacific Gas and Electric Company

Approved Meeting Minutes Standards Committee

California Independent System Operator Corporation Fifth Replacement Tariff. Appendix B.8 Utility Distribution Company Operating Agreement (UDCOA)

Bath Electric Gas & Water Systems

131 FERC 61,039 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

A REPORT BY THE NEW YORK STATE OFFICE OF THE STATE COMPTROLLER

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) ) ) ) ) ) ) ) ) ) ) )

AMENDED AND RESTATED BYLAWS TEXAS RELIABILITY ENTITY, INC.

130 FERC 61,051 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER APPROVING RELIABILITY STANDARD. (Issued January 21, 2010)

Introduction. Standard Processes Manual VERSION 3.0: Effective: June 26,

North American Energy Standards Board Standards Development Process

Texas Reliability Entity Standards Development Process

State of New Jersey DEPARTMENT OF THE PUBLIC ADVOCATE DIVISION OF RATE COUNSEL 31 CLINTON STREET, 11 TH FL P. O. BOX NEWARK, NEW JERSEY 07101

Meeting Minutes Compliance and Certification Committee September 16, :00 p.m. - 5:00 p.m. CT September 17, :00 a.m.

December 18, Filing of PSP Agreement with Placer County Water Agency

ESCO OPERATING AGREEMENT AND RETAIL TRANSMISSION SERVICE AGREEMENT

January 4, Filing of Service Agreement No Docket No. ER

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

ReliabilityFirst Corporation Reliability Standards Development Procedure Version 4

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. NORTH AMERICAN ELECTRIC ) Docket No. RR RELIABILITY CORPORATION )

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. North American Electric Reliability ) Docket No. RR16- Corporation )

IEEE PES STATIONARY BATTERY COMMITTEE

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

IEEE PES STATIONARY BATTERY COMMITTEE

July 5, PJM Interconnection, L.L.C., Docket No. ER17- Amendment to Service Agreement No. 4597; Queue No. AB2-048

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

Utility Regulation in the District of Columbia

ESCO OPERATING AGREEMENT

FRCC REGIONAL RELIABILITY STANDARD DEVELOPMENT PROCESS MANUAL

RELIABILITY STANDARDS DEVELOPMENT PROCEDURES

Procedures and Process for Development of ISO Rules and Filing of ISO Rules with the Alberta Utilities Commission

Minutes Planning Committee Teleconference/Web Meeting

DRAFT Meeting Minutes NAESB-NERC MOU Drafting Team October 15, 2002 Washington, DC

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) ) )

Conference Call and WebEx Notes Disturbance Monitoring Standard Drafting Team

BEFORE THE PUBLIC UTILITY COMMISSION OF OREGON UM 1610 ) ) ) ) ) ) ) ) ) ) I. INTRODUCTION

150 FERC 61,212 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

An Update on Federal Matters Affecting Large Energy Consumers

Agenda Standards Committee Process Subcommittee Meeting September 12, :00 5:00 p.m. Pacific

Transcription:

FINAL New York State Reliability Council (NYSRC) Reliability Rules Subcommittee (RRS) Minutes of Meeting #17 Con Edison Energy Control Center, New York City, NY Friday, October 6, 2000 Attendance Mayer Sasson (Chairman) Con Edison Member Roger Clayton* (Secretary) PG&E National Energy Group Member Keith O'Neal New York State PSC Member Steve Corey*** NYISO Member Larry Eng* Niagara Mohawk Power Corp. Member Larry Hochberg New York Power Authority Member Phil Davis*** KeySpan Energy Member Ray Kinney* New York State Electric and Gas Corp. Member Pat Callahan*** Rochester Gas & Electric Member Alan Adamson Consultant Joe Fleury*** New York State Electric and Gas Corp. Representing Ray Kinney * = Did not attend, ** =Attended part time, *** =Attended part time by phone 1.0 Introduction Mr. Hochberg took the minutes in Mr. Clayton's absence. 1.1 Request for Additional Agenda Items The posted agenda was discussed and amended as Additional Agenda Items 5.1-5.3 covered later on in these minutes. There being no further discussion, the amended agenda was adopted. 1.2 Topics for Open Session The open session agenda items were reviewed in preparation for the open session. 2.0 Meeting Minutes/Action Items 11/09/00 NYSRC RRS17 Final Minutes 1

2.1 Approval of RRS Minutes #16 The RRS Meeting #16 Minutes were unanimously approved with minor revisions. 2.2 Action Item List The Action Item list was reviewed. An updated action item list is attached. Regarding AI 11-7, it was reported that NPCC document being developed by CO-9 is not yet ready. Mr. Davis will provide RRS with the status of NYISO comments on the document (AI 17-1). AI's 14-1, 14-3, 16-1 through 16-4 were completed. Regarding AI 15-1, Mr. Adamson had sent RRS drafts of the statewide reliability study. He was requested to issue an updated draft of the statewide study (AI 17-2). Messrs. Davis and O'Neal noted that Mr. Clayton had sent out a press release indicating that the California ISO is permitted to violate NOx emissions limits. The release will be discussed at the next RRS meeting (AI 14-3). 3.0 Report on NYSRC EC Meeting #17 Mr. Fleury provided the following status report: The 2001 budget is $500,000 and has not yet been approved. The EC is exploring funding of the NYSRC through a TO transmission surcharge. Mr. Loehr volunteered to fill the post of Public Information Chairman. The EC was updated on the status of the Statewide reliability study, NYISO studies and the discussions RRS had with Columbia Gas Transmission on the Millennium project. Status reports were provided on RRS, ICAP WG and RCMS activities. 4.0 NYSRC RR Development Mr. O'Neal had issued RRS a draft template for potential rule #30. Due to time constraints, discussion of potential RR changes was postponed until the next RRS meeting. Potential Rule Change Assignee RRS Action 1. New knee of the curve P-V criterion S. Corey Prepare template 2. Planning responsibility (NY ISO TEI 5.3) N/A NYISO issue Remove from list 3. Prioritization. Planning by queue position N/A NYISO issue Remove from list or by group. 4. Definition of BPS S. Corey Prepare template 5. Provision for Emergency Actions K. O'Neal Template completed 6. Reserve requirements as a function of Remove from list demand elasticity 11/09/00 NYSRC RRS17 Final Minutes 2

7. Study impact of changes to ICAP 1/10 ICAP WG 2001 IRM study. & EOP criteria Remove from list. 8. Reactive load and resource PF requirements S. Corey Prepare template at BPS/LSE boundary 9. Normal/extreme contingency definition S. Corey Prepare template 10. Incremental impact criterion S. Corey Remove from list 11. CBM/TRM issues R. Clayton Remove from list 12. Disturbance reporting L. Eng Coordinate with NYISO disturbance reporting 13. Long term reserve requirements K. O Neal (ISO/RC Agreement, Article 4.5) 14. ICAP assumptions on generators to ICAP WG 2001 IRM study be included in study Remove from list 15. Replacement Operating Reserve K. O Neal (T) Completed. Remove from list. 16. Quick Start Mode for 30-Minute GTs M. Sasson (T) Completed. Remove at Gowanus & Narrows from list. 17. Impact of local RR on local and ICAP WG 2001 IRM study state wide reserve requirements Remove from list 18. Special Protection Systems Application R. Clayton Template completed Criteria 19. 15 minute reserve criterion Remove from list. 20. Multiple utilities on same ROW V. Kotecha R.Clayton to research 21. Restoration criteria M. Sasson Assignee added. 22. Protection criteria S. Corey Prepare template 23. Generator Unit Availability A. Adamson Completed. Remove Data Requirements from list 24. Interconnection requirements J. Adams to discuss with S. Corey. 25. NOx Emissions DEC criteria and M. Sasson Draft policy statement impact on dispatch in NYC tabled by EC 26. Equipment maintenance criteria P. Davis Remove from list. 27. System data maintenance Description of potential rule required 28. Ramp-rate reserve criterion M. Sasson Obtain NYISO comment on template 29. Short-circuit criterion S. Corey Prepare template 30. NYCA state performance K. O Neal Prepare template 4.1 Approval of RR rev1 11/09/00 NYSRC RRS17 Final Minutes 3

Mr. Fleury reported that all comments he has received will be incorporated into the draft RR manual rev.1 and he will send it back to RRS for another review. 4.2 Introductory wording to "Applications of Reliability Rules" for web site As requested by the EC, RRS discussed several issues regarding the List of Applications of NYSRC Reliability Rules including Local Reliability Rules (List). It is understood that this List is to be included in the next revision of the NYISO Transmission and Dispatching Operations Manual. The issues and recommendations follow: Responsibility for keeping/documenting existing List RRS recommended that the official List should be kept and maintained up-to-date by the NYISO. RRS also agreed that it would be most appropriate for the NYISO to keep the official List in the NYISO T&D Operations Manual with a copy of the List posted to the NYSRC web site. Process for making changes to the existing List or adding new applications to the List The RRS discussed the genesis of the applications from TO operating procedures that existed prior to the formation of the NYISO. RRS noted that the applications were documented because specific operating procedures were (and still are) needed to maintain compliance with the reliability rules in all areas of the BPS, including areas not secured by the NYPP (NYISO) or where the NYPP (NYISO) did not have the resources to develop procedures on its own. In addition, the applications would preserve the ability of the transmission owners to execute certain operating procedures to comply with the reliability rules, including the local reliability rules. RRS recommended that new applications or changes to existing applications could be requested by the NYISO, the TO or the NYSRC. This process typically would be a cooperative effort between the TO and NYSIO or all three entities. When changes are finalized, the NYISO would update the List and provide a copy to the NYSRC for posting on its web site. Compliance monitoring of applications RRS recommended that RCMS, in monitoring compliance with the NYSRC Rules, should provide an oversight review of the applications. RCMS would review the List to assure that the application is appropriate to the corresponding Rule and that the TO or NYISO is maintaining and using the operating procedure summarized by the application. Wording of Introduction for NYSRC web site 11/09/00 NYSRC RRS17 Final Minutes 4

Mr. Hochberg provided comments on the draft Introductory wording. Mr. Sasson will add a section summarizing the above points RRS had agreed to recommend and will send out the revised Introduction to RRS. (AI 17-4). Mr. Callahan had e-mailed an update to one of the RG&E applications on the List. 4.3 NPCC A6 compliance documentation Mr. Adamson reported that the NPCC Compliance Monitoring Subcommittee will be performing a pilot audit of the NYISO's compliance with the NPCC A-6 Operating Reserve Criteria on November 2. Mr. John Muir of RCMS and Mr. Adamson plan to attend as observers. Mr. Adamson will request to have the information in the draft letter he sent to RRS (AI 16-1) incorporated into the audit. Thus, further consideration of AI's 14-2, 14-5 and 16-1 will be postponed pending the results of the audit. Mr. Davis again indicated that the NYISO does not have enough AGC reserve and that reserve pick-ups should be done for contingencies, not load pick-ups. This issue is still under consideration by RRS (potential rule #28) and the NPCC pilot audit results may provide additional guidance. 4.4 ICAP Procurement Period Mr. O'Neal raised a reliability concern about the NYISO changing the ICAP procurement period from 6 months to 1 month. A study of this issue indicated no reliability concern. Mr. O'Neal raised the question of how the ICAP can be assured to be available only 1 month ahead as a practical matter if generation owners sell ICAP seasonably to other markets. Mr. Sasson will raise this issue at the next EC meeting. 5.0 Additional Agenda Items 5.1 Report on NYISO SOAS Operating Reserve Issues Mr. O'Neal indicated a concern about how the NYISO is going to comply with the NYSRC reserve replenishment rule. Discussion was postponed until the next meeting. 5.2 Scope of Next Update to NYSRC Rules Manual Mr. Adamson had provided a document with suggestions for several areas of review. Discussion was postponed until the next meeting. 5.3 NYCA Capacity Situation for Summer 2001 Several RRS members expressed concern about meeting capacity requirements for summer 2001. Mr. Adamson stated that RCMS had expressed similar concerns and would raise this issue at the next EC meeting. Mr. O'Neal expressed concern that if the normal process for siting power plants is followed, 11/09/00 NYSRC RRS17 Final Minutes 5

this could end up delaying some planned capacity installations beyond the summer peak period. He indicated that a declaration by the NYSRC to the NYS PSC of an emergency capacity deficiency would expedite the siting process. RRS agreed that the expected range of capacity/load for summer 2001 needs to be quantified and presented at the next EC meeting for discussion. Also, Mr. Davis expressed a concern about a discrepancy between the LIPA/NYC transfer limits reported by the NYISO vs. the limit reported by LIPA Operators. Mr. Corey reviewed capacity additions with planned in service dates for the summer of 2001 (in addition to the NYPA gas turbines) and these included: East Coast Power (Linden CoGen) @ 250MW; Kent Ave.-NYC Energy LLP @ 79.9MW; 1 st Rochdale Bronx @ 79.9MW; 1 st Rochdale Brooklyn @ 79.9MW; LI Enron Far Rockaway Barge @ 60MW. Mr. Adamson indicated that the base load forecast (50 percentile) for NYCA for summer 2001 is 30,500MW and the extreme (90 percentile) forecast is 31,800MW. Mr. Corey also reported that Mr. Museler requested a review of transmission line thermal ratings to identify the type and location of limiting elements to determine if circuit ratings could be raised by simple replacement of CTs, line traps or other relatively inexpensive equipment. RRS agreed to request the NYISO to prepare a load and capacity analysis for summer 2001 that should examine the base and extreme load forecast and assume an 18% IRM. The analysis should include statewide, NYC (80%) and LI (93%) requirements. Mr. Adamson is to prepare and send the request to the NYSIO on behalf of RRS (AI 17-3). 6.0 Open Session The open session ran from 1300 to 1420 with several participants on line. 6.1 NYSRC ICAP WG Report Mr. Adamson reviewed the draft list of assumptions for the NYSRC 2001-2002 IRM Study. Several RRS comments were noted: Mr. Hochberg indicated that the capacity rating of the NYPA GTs had not been finalized yet and that NYPA would provide it within a few days. Mr. Sasson requested that the 1% IRM adder be separately stated in the report and that Appendix A should spell out all of its components e.g. NOx restrictions, high temperatures affecting GT ratings, new market structure, cycling of GTs effecting availability etc. Mr. Sasson suggested examining a combined sensitivity case to get a feel for the IRM requirement for a feasible worst case scenario. RRS agreed to request ICAP WG do a combined 50% of planned capacity, 90% extreme load, no PJM emergency assistance and no voltage reduction statewide sensitivity run. Mr. Adamson requested RRS to review the transfer limits used by the transmission model (this would address the above concern raised by Mr. Davis). Mr. Adamson will revise the assumptions list and issue to RRS and ICAP WG (AI 17-5). 11/09/00 NYSRC RRS17 Final Minutes 6

Mr. Fleury provided several comments on the draft Appendix A. Mr. Hochberg noted again the 517MW capacity indicated for NYPA GTs in Appendix A was preliminary. Mr. Adamson recommended that the 5 year averages be removed from Table A-3 since the study uses 10 year averages. Any further comments should be brought up at the EC meeting on 10/17 where approval of the study assumptions will be on the agenda. During the closed session Mr. O'Neal raised a concern about the Astoria 2 unit not having the capacity assumed in the IRM study. Mr. Sasson elaborated that this is another case of NOx limited generator constraints not being modeled correctly both in the IRM study as well as in the NYISO day-ahead schedule. Mr. Sasson indicated that Con Edison has requested FERC and the NYISO to review this matter since Astoria 2 is bidding full capacity into the ICAP market without considering the NOx constraints. RRS agreed to determine more precisely what the restrictions are on Astoria 2 and try to model them correctly in the IRM study. Mr. Adamson was requested to follow up (AI 17-6). Mr. Adamson reviewed the study schedule. MARS preliminary results are scheduled for approval by ICAP WG on 10/18 with a final draft report by 11/15. EC approval of the study is scheduled for the 12/11 meeting. Mr. Sasson will request Mr. Cordeiro, head of the ICAP WG, to hold a joint meeting early in December. Mr. Adamson noted that the report will compare results with last year's study instead of previous NYPP studies. 6.2 NYSRC RCMS Report (NYISO Compliance) Mr. Adamson reported the RCMS had met September 28 and provided the following status report: RCMS will be performing a compliance assessment of the NYSRC's five local reliability rules. RCMS completed reviewing the NERC phase 2 assessment. RCMS is developing a new Policy 4 that will be a procedure for compliance reviews-- it is expected to be on the agenda for the November EC meeting. RCMS is developing compliance templates for certain NYSRC rules--the templates will include measurements and levels of non-compliance similar to NPCC/NERC format. 6.3 NYSRC RRS Report (NERC/NPCC Compliance) Mr. Adamson reported that there has been no further progress on merging the NERC rules into the NPCC rules manual. 6.4 NYSRC RR Development Report 11/09/00 NYSRC RRS17 Final Minutes 7

Mr. Sasson reported that the rev. 1 of the Rules manual will be posted to the NYSRC web site as soon as it is finalized. He also reported that the EC is looking to place on the NYSRC web site the List of Applications of NYSRC Reliability Rules including Local Reliability Rules that is to be included in the NYISO T&D Operations Manual. There were no new requests for new rules. The Council is still reviewing a few that already had been submitted. 7.0 Next Meeting RRS Meeting #18 is scheduled at NYISO on Thursday, November 2, 2000 @ 1000. RRS Meeting #19 is scheduled at NYISO on Thursday, December 7, 2000 @ 1000. Final Minutes of Meeting #17. Submitted to RRS by Larry Hochberg on November 6, 2000. 11/09/00 NYSRC RRS17 Final Minutes 8